Yokogawa RAMC User Manual

Page 62

Advertising
background image

<7. HART-COMMUNICATION>

7-14

IM 01R01B02-00E-E 10th edition January 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

Device setup

Detailed setup
Configure signal

Total

reset

Reset

totalizer

Device setup

Detailed setup
Configure signal

Temperature

unit

degC / degF

Select temperature unit

Device setup

Detailed setup
Configure output

Analog output

Indication, test and adjustment of current output :

Flow AO

Read Current output in mA

AO Alm typ

Lo current < 3,6mA at error

Hi current > 21.0mA at error

Loop Test

Set the analogue output fix to 4mA, 20mA or arbitrary current.

Finish with ´End´.

D/A Trim

Adjustment of current output at 4mA and 20mA.

Device setup

Detailed setup
Configure output

HART output

HART

®

specific parameter :

Poll Addr

Poll Address (Function see above) (Def.: 0)

Num req preams Number of leading FF to HART

®

unit (Def.: 5)

Num resp pream Number of leading FF from HART

®

-unit (Def.:5)

Device setup

Detailed setup

Display

selection

Selection of measuring value on display,

Different if manual calibration is activated.

For standard calibration table:

Flow / Totalizer / Temperature

For manual calibration table:

Percent / Temperature