<6. ELECTRONIC TRANSMITTER (-E)>

6-8

IM 01R01B02-00E-E 10th edition January 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

6.2.5 Setting of damping (F2-)

Function F21 allows damping the output with a certain time constant (63% value). Normally the time constant
is set to 1 sec.
The selection of the time constant is as follows:

Description

Selection

Key

Indication

Change to setting mode

Enter

Display mode
F1-

Setting mode

Enter

F2-
F21

Selection damping
constant
or

or

or

0 s
1 s

5 s

10 s

Enter
Enter

Enter

2 x →

Enter

3 x →

Enter

F21 0
F21
F21 1
F21
F21 5
F21
F21 10
F21

Back to display mode

F2-
Display mode

Note: If you press “↑" instead of “Enter”, you can return from the selected point to the previous menu

without activating the displayed parameter.

6.2.6 Selection / Adjustment 4-20 mA / 0-20 mA (F3-)

Function F3- sets the current output to 4-20 mA or 0-20 mA. In addition, offset and span have to be
readjusted. Offset compensation is for fine tuning the 0 or 4 mA point. Span or range compensation is for
precise adjustment of the 20 mA point.
For compensating the output, an ampere metre (mA) should be connected to the circuit loop. For wiring refer
to the diagrams in chapter 3.
The current output is set according to customer specifications at the factory.
Switching the output is executed as follows:

Description

Selection

Key

Indication

Change to setting mode

Enter

Display mode
F1-

Setting mode
Output selection

2 x →

Enter
Enter

F3-
F31
F31 0-20

Selection
or

0-20
4-20

Enter

Enter

F31
F31 4-20
F31

Setting function
Offset-Adjustment

Enter

F32
F32 00

Offset-Adjustment
(Setting current to 0/4 mA)

Increase
Decrease
if 0/4 mA

Enter

F32 in steps of +1 (+20 µA)
F32 in steps of -1 (-20 µA)
F32

Setting function
Span setting

Enter

F33
F33 0

Span setting
(Setting current to 20 mA)

Increase
Decrease
if 20 mA

Enter

F33 in steps of +1 (+20 µA)
F33 in steps of -1 (-20 µA)
F33

Back to display mode

F3-
Display mode