<2. Notes on Handling>

2-4

IM 01C50E01-01EN

WARNING

The battery pack may be replaced in a

hazardous area. The battery pack has

surface resistivity greater than 1G ohm and

must be properly installed in the enclosure

of the transmitter. Care must be taken during

transportation to and from the point of installation

to prevent electrostatic charge build-up.

2.7.1 FM Approval

Caution for FM intrinsically safe type. (Following

contents refer “DOC. No. IFM038-A20”)
Note 1. Model YTA Series temperature transmitters

with optional code /FS17 are applicable for

use in hazardous locations.

• Applicable Standard: Class 3600, Class

3610, Class 3611, Class 3810, NEMA 250,

ANSI/ISA-60079-0, ANSI/ISA-60079-11

• Intrinsically Safe for Class I, Division 1,

Groups A, B, C & D, Class II, Division 1,

Groups E, F & G and Class III, Division1,

Class I, Zone 0, in Hazardous Locations,

AEx ia IIC

• Nonincendive for Class I, Division 2,

Groups A, B, C & D, Class II, Division 2,

Groups F & G and Class III, Division 1,

Class I, Zone 2,

Groups IIC, in Hazardous Locations.

• Enclosure: NEMA 4X (Indoors and outdoors)

• Temperature Class: T4

• Ambient temperature: –50 to 70°C

Note 2. Output Parameters

• Sensor Circuit ( 1 to 5 )

Maximum Output Voltage Voc: 6.6V

Maximum Output Current Isc: 66mA

Maximum Output Power Po: 109mW

Maximum External Capacitance Ca: 22uF

Maximum External Inductance La: 8.1mH

• The above parameters apply when one of

the two conditions below is given:

- the total Li of the external circuit (excluding

the cable) is < 1% of the La value or

- the total Ci of the external circuit (excluding

the cable) is < 1% of the Ca value.

• The above parameters are reduced to 50%

when both of the two conditions below are

given:

- the total Li of the external circuit (excluding

the cable) is ≥ 1% of the La value and

- the total Ci of the external circuit (excluding

the cable) is ≥ 1% of the Ca value.

• The reduced capacitance of the external

circuit (including cable) shall not be greater

than 1μF for Group IIB and 600nF for Group

IIC.

• For the sensor input circuitry, these entity

parameters must be taken into account

when installed.

• Installation Requirements between

temperature transmitter and sensor:

Voc ≤ Vsi, Isc ≤ Isi, Po ≤ Psi

Ca ≥ Co + Ccable, La ≥Lo + Lcable

Vsi, Isi, Psi, Co and Lo are parameters of the sensor.

• Wiring for Nonincendive according to

Nonincendive field wiring standard.

Note 3. Installation

• Installation should be in accordance with

ANSI/ISA RP12.6 “Installation of Intrinsically

Safe Systems for Hazardous (Classified)

Locations” and the National Electric Code

(ANSI/NFPA 70).

• Dust-tight conduit seal must be used when

installed in a Class II, III, Group E, F and G

environments.

• Note a warning label worded

“SUBSTITUTION OF COMPONENTS MAY

IMPAIR INTRINSIC SAFETY,” and

“INSTALL IN ACCORDANCE WITH DOC.

NO. IFM038-A20”.