<8. Maintenance>

8-10

IM 01C50E01-01EN

Integral

indicator

Factory

NAMUR

category

Bit

Diagnostic

Status

Diagnostic

Status Detail

Cause

Release/

recovery

conditions

(except

restart)

Output

Operation

Action

AL.50

S1.SPAN

C

Bit

25

Faults in

sensor or

actuator

element

SENSOR1

SPAN ADJ

ERR

Sensor 1 input

adjustment range

error

Recovers

when the

input is within

the range.

Normal action

Check

the input

adjustment

setting.

AL.51

S1.ZERO

SENSOR1

ZERO ADJ

ERR

Sensor 1 input

adjustment value

error

Recovers

when the

input value

is a normal

value.

Normal action

Check

the input

adjustment

setting.

AL.52

S2.SPAN

*4

SENSOR2

SPAN ADJ

ERR

Sensor 2 input

adjustment range

error

Recovers

when the

input is within

the range.

Normal action

Check

the input

adjustment

setting.

AL.53

S2.ZERO

*4

SENSOR2

ZERO ADJ

ERR

Sensor 2 input

adjustment value

error

Recovers

when the

input value

is a normal

value.

Normal action

Check

the input

adjustment

setting.

AL.60

AI1.OS

Bit

24

Out of service

AI1 O/S

MODE

AI1 block is O/S

mode.

Recovers

when the

mode target

of AI1 block

is other than

O/S.

Hold

Check the

AI1 block

setting.

AL.61

AI2.OS

*4

AI2 O/S

MODE

AI2 block is O/S

mode.

Recovers

when the

mode target

of AI1 block

is other than

O/S.

Hold

Check the

AI2 block

setting.

AL.64

AI1.SIM

Bit

17

Simulation is

active

AI1

SIMULATE

MODE

Simulate Switch

of the AI1 block is

enabled

Recovers

when the

Simulate

Switch of AI1

block is set

to DISABLE.

Normal action

Check the

AI1 block

setting.

AL.65

AI2.SIM

*4

AI2

SIMULATE

MODE

Simulate Switch

of the AI2 block is

enabled

Recovers

when the

Simulate

Switch of AI2

block is set

to DISABLE.

Normal action

Check the

AI2 block

setting.

*1: “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off

specification) according to NAMUR NE107*.

* NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”

*2: When the device detects “AL02 AMP.ERR,” “AL03 FUP.ERR,” “AL10 S1.FAIL,” “AL11 S2.FAIL,” and “AL12 RJ.FAIL”, the LCD

display stays on regardless of the status in LCD mode.

*3:

When the ambient temperature is higher than 60°C, AL.70 may be generated despite the indication of Energy Left shows sufficiently

remained. However, it does not affect the device operation. This is caused by the change of battery inner status with extremely

low power consumption under high temperature environment. It is recommended to set the data updating period to 15 seconds or

shorter.

*4:

Applicable for dual input type with detachable antenna, Amplifier housing code 8 and 9.

*5:

Applicable for single input type with integral antenna, Amplifier housing code 7.