<2. Notes on Handling>

2-5

IM 01C50E01-01EN

Temperature

Transmitter

Battery

pack

1
2
3
4
5

1
2
3
4
5

Temperature

Transmitter

Battery

pack

Temperature Sensor (*1)

Amplifier housing code other than 7

Hazardous Location

Antenna

(*1)

Arrester

(*1, *2)

Temperature Sensor (*1)

(One or Two sensors)

*1: These apparatus are simple apparatus.

*2: Arrester may not be connected.

Antenna Connector

F0204.ai

[Installation Diagram]

Amplifier housing code 7

Hazardous Location

Note 4. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void FM

Approvals approval.

Note 5. Battery Pack

USE ONLY BATTERY PACK YOKOGAWA

F9915MA OR F9915NS.

Note 6. Special Conditions for safe use

POTENTIAL ELECTROSTATIC CHARGING

HAZARD-SECURE DISTANCE OF 100MM

FROM ANTENNA.

DO NOT OPEN WHEN CL II, III, DIV 1,2

ATMOSPHERE IS PRESENT.

2.7.2 CSA Certification

Caution for CSA intrinsically safe type. (Following

contents refer “DOC. No. ICS031)
Note 1. Model YTA Series temperature transmitters

with optional code /CS17 are applicable for

use in hazardous locations.

Certificate: 2328785

• Applicable standard: CAN/CSA-C22.2 No.0,

CAN/CSA-C22.2 No.0.4, C22.2 No.25,

CAN/CSA-C22.2 No.94,

CAN/CSA-C22.2 No.157, C22.2 No.213,

CAN/CSA-C22.2 No.61010-1,

CAN/CSA- C22.2 No.60079-0,

CAN/CSA-E60079-11, IEC60529

• Ex ia IIC T4

• Intrinsically Safe for Class I, Division 1,

Groups A, B, C & D, Class II, Division 1,

Groups E, F & G, Class III, Division 1

• Nonincendive for Class I, Division2,

Groups A, B, C & D, Class II, Division2,

Groups F & G, Class III, Division1

• Enclosure: IP66/IP67 and Type 4X

• Temperature Code: T4

• Ambient Temperature: –50 to 70°C

Note 2. Output Parameters

• Sensor Circuit (Terminals: 1 to 5)

Uo = 6.6 V, Io = 66 mA,

Po = 109 mW, Co = 22 μF,

Lo = 8.1 mH

• The above parameters apply when one of

the two conditions below is given:

- the total Li of the external circuit (excluding

the cable) is < 1% of the Lo value or

- the total Ci of the external circuit (excluding

the cable) is < 1% of the Co value.

• The above parameters are reduced to 50%

when both of the two conditions below are

given:

- the total Li of the external circuit (excluding

the cable) is ≥ 1% of the Lo value and

- the total Ci of the external circuit (excluding

the cable) is ≥ 1% of the Co value.

• The reduced capacitance of the external

circuit (including cable) shall not be greater

than 1μF for Group IIB and 600nF for Group

IIC.

Note 3. Installation

• Installation should be in accordance with

Canadian Electrical Code Part I and Local

Electrical Code.

• The Hand Held Terminal must be CSA

certified.

• Do not alter drawing without authorization

from CSA.

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void

Canadian Standards Intrinsically safe and

nonincendive Certification.