Parameter summary, Parameter summary -1 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 62

Advertising
background image

<9. Parameter Summary>

9-1

IM 01C50E01-01EN

9. Parameter Summary

Table 9.1

Parameter Summary

Object

ID

Attribute

ID

Label

Description

Default value Handling

1.

UAPMO

block

1

Version Revision Indicates the application revision of YTA. This revision changes

when the application software is downloaded.

---

R

10

Static Revision

Indicates the revision level of the fixed parameters of UAP.

Used, for example, to check whether parameters have been

changed.

0

R

64

Identification

Number

Indicates the vendor ID, model ID, and revision of the device.

---

R

65

CTS Version

Indicates the version of the communication stack test system

(CTS).

0

R

66

ITS Version

Indicates the version of the interoperability test system (ITS).

0

R

67

Diagnostic Status Indicates the diagnostic results of the device based on the

NAMUR NE107

*1

model.

Setting Enable diagnostic status configuration in UAP Option to

Enable allows turning OFF and ON the display of the diagnostic

results for each summary, and changing Categorize. For

Categorize at the time of shipment, refer to tables 8.3 and 10.2.

---

R

68

UAP Option

Allows setting the Diagnostic Status and write protection of UAP.

Software write protect

1: On, 0: Off

Enable hardware write protect

1: Enable, 0: Disable (default)

Enable diagnostic status configuration

1: Enable, 0: Disable (default)

The following table shows the relationship between the

hardware write protection and software write protection.

Enable

hardware

write

protect

Hardware

write

protect

Software write

protect

Write

protect

Disable

Off or On

Off

No

Disable

Off or On

On

Protected

Enable

Off

Off or On

No

Enable

On

Off or On

Protected

0

W

69

Diagnostic Switch Allows setting On/Off for each summary of Diagnostic Status

when Enable diagnostic status configuration in UAP Option is

set to Enable.

On

W

70

Diagnostic

Configuration

Allows Categorize for each summary of Diagnostic Status when

Enable diagnostic status configuration in UAP Option is set to

Enable.

Refer to Table

9.2.

W

102

Diagnostic Status

Detail

Detailed information on Diagnostic Status. For Categorize at the

time of shipment, refer to Table 9.2.

Refer to Table

9.2.

R

103

Energy Left

Indicates the number of days of remaining battery life assuming

ambient temperature condition as 23 degrees Celsius. The unit

is day.

---

R

104

Reset Energy Left Resets the remaining battery power calculation to restore it to

a remaining battery power calculation which is based on new

batteries.

0 = Continue

1 = Reset

0 (reading

value is

always 0)

W

105

Power Supply

Status

Indicates remaining battery life and power supply of device

0 – line powered

1 – battery powered, greater than 75% remaining capacity

2 – battery powered, between 25% and 75% remaining

capacity

3 – battery powered, less than 25% remaining capacity

---

R

Note: TSAP ID is 2.