<6. Operation>

6-1

IM 01C50E01-01EN

6. Operation

6.1 Preparation for Starting

Operation

NOTE

It is required to set security and network

information to enable the transmitter to be

connected to the Field Wireless Network. For

more details, refer to subsection 6.4 “Connecting

to the Field Wireless Network”.

1) Checking Installation and Wiring

Ensure that the transmitter is installed correctly

and the temperature sensor is connected

correctly according to the procedures described

in section 4 “Installation”, and section 5 “Wiring”.

When connecting the thermocouple, particular

attention needs to be paid because the

transmitter cannot detect a wrong polarity

connection.

2) Insert batteries into the battery case, and install

to the transmitter. To insert batteries into the

battery case, be careful to polarity of batteries

and battery case. For details of Installation of

battery, refer to section 8.4.5 and 8.4.6.

Battery case is installed in the transmitter when

shipped from the factory, however, batteries are

sold separately and not included.

3) Using the device configuration tool confirm

that transmitter is operation properly. Check

parameter values or change the setpoints as

necessary.

If the transmitter is equipped with an integral

indicator, its indication can be used to confirm

that the transmitter is operating properly.

For details on how to confirm this, refer to

subsection 7.4 “Self-Diagnostics.”

ISA100 devices display self-diagnostic

information in an easy-to-understand manner

using four categories (Check function,

Maintenance required, Failure, and Off

specification) according to NAMUR NE107*

* NAMUR NE107 “Self-Monitoring and Diagnosis of Field

Devices”

■ Confirm that transmitter is operating

properly by integral indicator.

If the transmitter is faulty, an error code is displayed.

F0601.ai

Self-diagnostic error on the integral indicator

(Faulty transmitter)

Figure 6.1 Integral Indicator with Error Code

NOTE

If any of the above errors are indicated on the

display of the integral indicator or the device

configuration tool, refer to subsection 8.5.3 for

the corrective action.

Verify and Change Transmitter Parameter

Setting and Values

The parameters related to the following items are

set at factory as specified in order.

• Input sensor type

• Connection of RTD

• Measurement range (measurement lower/

upper limit, unit)