<2. Notes on Handling>

2-8

IM 01C50E01-01EN

2.7.4 IECEx Certification

Caution for IECEx Intrinsically safe type.
Note 1. Model YTA Series temperature transmitters

with optional code /SS27 for potentially

explosive atmospheres:

• No. IECEx KEM 10.0073X

• Applicable Standard:

IEC 60079-0: 2011, IEC 60079-11: 2011,

IEC 60079-26: 2006

• Type of Protection and Marking code:

Ex ia IIC T4 Ga

• Ambient Temperature: –50°C to 70°C

• Enclosure: IP66/IP67

Note 2. Output Parameters

• Sensor input circuit (Terminals 1 to 5 )

Uo: 6.6 V

Io: 66 mA

Po: 109 mW

Co: 22 μF

Lo: 8.1 mH

• For the sensor input circuitry, these entity

parameters must be taken into account when

installed.

• The above parameters apply when one of

the two conditions below is given:

- the total Li of the external circuit (excluding

the cable) is < 1% of the Lo value or

- the total Ci of the external circuit (excluding

the cable) is < 1% of the Co value.

• The above parameters are reduced to 50%

when both of the two conditions below are

given:

- the total Li of the external circuit (excluding

the cable) is ≥ 1% of the Lo value and

- the total Ci of the external circuit (excluding

the cable) is ≥ 1% of the Co value.

• The reduced capacitance of the external

circuit (including cable) shall not be greater

than 1μF for Group IIB and 600nF for Group

IIC.

Note 3. Installation

• Installation should be in accordance with

local installation requirements.

(Refer to the Control Drawing)

Temperature

Transmitter

Battery

pack

1
2
3
4
5

1
2
3
4
5

Temperature

Transmitter

Battery

pack

Temperature Sensor (*1)

Amplifier housing code 8 and 9

Hazardous area

Antenna

(*1)

Arrester

(*1, *2)

Temperature Sensor (*1)

(One or Two sensors)

*1: These apparatus are simple apparatus.

*2: Arrester may not be connected.

Antenna Connector

F0209.ai

[Control Drawing]

Amplifier housing code 7

Hazardous area

Note 4. Maintenance and Repair

WARNING

The instrument modification or parts replacement

by other than an authorized Representative of

Yokogawa Electric Corporation is prohibited and

will void IECEx Intrinsically safe Certification.

Note 5. Battery Pack

• Use only YOKOGAWA battery pack

F9915MA or F9915NS.

Note 6. Special conditions for Safe Use

• In case of the aluminum enclosure, if the

Transmitter is mounted in an area where the

use of EPL Ga apparatus is required, it must

be installed such, that, even in the event rare

incidents, ingition source due to impact and

friction sparks are excluded.

• For application in an area where the use of

EPL Ga apparatus is required, electrostatic

charge on the non-metallic parts of the

Temperature Transmitter shall be avoided.