<7. Setting Parameters>

7-18

IM 01C50E01-01EN

Checking the Diagnostic Status category allows

taking the proper action. The Diagnostic Status

contents are common for all ISA devices, and the

setting for the Diagnostic Status category can be

changed. For further details, refer to Diagnostic

Status Detail.

In Diagnostic Status Contents that can be

diagnosed by the YTA, the alert category set in Out

of Service can be changed to Check function. To do

so, follow one of the two procedures below.

a) UAPMO block: UAP Option select “enable”.

b) UAPMO block: Diagnostic Configuration

change Out of Service from “Failure” to

Check function.

c) UAPMO block: UAP Option select “disable“.

The contents of diagnostic status are defined either

valid or invalid at Diagnostic Switch parameter.

Follow the example below to change “Out of

Service” to invalid.

a) UAPMO block: UAP Option select “enable“.

b) UAPMO block: Diagnostic Switch turn “Off“

for Out of Service.

c) UAPMO block: UAP Option select “disable“.

Note: Be careful when changing the alert category and turning

detection on and off as described above. Be sure to set

UAP Option to disable again to prevent setting errors.

* NAMUR NE107 “Self-Monitoring and Diagnosis of Field

Devices”

In Diagnostic Configuration setting, select one from the

followings; F: Failure status, C: Function check status, O:

Out of specification status, or M: Maintenance required

status.

7.4.2 Alert Report

YTA generates alert information related to

Diagnostic Status and automatically sends to a field

wireless gateway. To use this function, the following

alert setting is necessary. When “Out of Service” for

Diagnostic Status alert is required, choose “FALSE”

for [Out of Service.Alert Disable] in the UAPMO

block. Refer to the field wireless gateway User’s

Manual for the setting procedure to obtain the alert

information from the gateway.

The alert report consists of the list of parameter

names as shown Table 7.3.

Table 7.3

Contents of Alert Report

Parameter name

Description

DetectObjectTLPort Alert detection port UAP

(0xF0B2) fixed

DetectObject

Alert detection block UAPMO (1)

fixed

DetectTime

Time stamp

AlertDirection

1: generated, 0: clear

AlertPriority

Alert priorities set by users

AlertType

Alert types, see 8.4 Self-

Diagnostics

AlertValue

NAMUR107 category

0:Failure,

1:checkFunction,

2:OffSpec,

3:MaintenaceRequired

CAUTION

For a wireless gateway which does not support

the alert report function, the alert setting in

UAPMO block for the transmitter must be set

to “Disable.” Note that YFGW710 field wireless

integrated gateway does not have the alert

report function.