4 tag and device information, 5 setup the integral indicator, 6 power saving mode setting – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 44: 7 unit, 8 measurement range, Tag and device information -12, Setup the integral indicator -12, Power saving mode setting -12, Unit -12, Measurement range -12

Advertising
background image

<7. Setting Parameters>

7-12

IM 01C50E01-01EN

7.3.4 Tag and Device Information

If these are specified when ordering, the designated

Tag No. and device information are set and

shipped.
Tag No. and device information can be checked as

follows.

■ Procedure to call up the tag No. and device

information
- Device Tag (Software Tag)

This is specified when writing characters

(up to 16 characters) that differ from those

specified in Tag No. to the amplifier tag.

For details on how to confirm this, refer to

subsection 6.4. ”Connecting to the Field

Wireless Network”.

- Tag Description

This is a universal parameter to store the

comment that describes the content of the

tag located in the TRANSDUCER and AI

blocks.

■ Limitation of Device Information

When changing the device information, input

the information based on the following limitation

on the number of characters.
- Message function (up to 32 characters)

TRANSDUCER block : Tag Description

AI1/AI2 block : Tag Description

7.3.5 Setup the Integral Indicator

As for the integral indicator display, either the

temperature, voltage, resistance or the % value

of the temperature, voltage, resistance can be

selected and displayed. The display is in the output

format of the process value.
Specify AI block to display on the LCD.

■ LCD display parameter (Display Selection)
Select AI block to display on the LCD from AI1

or AI2.

■ Call up the display parameter (Process Value

Type)

AI1 block: Configuration: Process Value Type
Either actual target value (Direct) or % (Indirect)

can be selected.

7.3.6 Power Saving Mode Setting

This function is applicable for dual input type with

a detachable antenna, Amplifier housing code

8 and 9. Enabling the power saving mode on

prolongs the battery life of the transmitter, in which

the transmitter's measurement and calcutattion

are suitable for general use with a gradual change

in the process and ambient temperature. On the

other hand, when the power saving mode is set to

off, the transmitter is capable of a steep change in

the process and ambient temperature wtih its high

responsiveness trading off of the battery life.

■ Procedure to call up the power saving mode
TRANSDUCER block : Power Saving Mode

Off: Disable

On: Enable

7.3.7 Unit

The unit for the process value is set at the factory.

The specified unit of the input sensors set (°C if not

specified).
When the unit of the temperature, voltage, and

resistance is displayed, set the Process Value Type

parameter to actual target value (Direct).
And sensor type set by the sensor type setting

parameter (Lin Type) must be corresponded with

the unit displayed.
When using the resistance temperature sensor or

the thermocouple sensor, unit displayed set °C or

others, using voltage, set mV, and using resistance,

set ohm.
The unit can be set by following the procedure

below.

■ Procedure to call up the unit parameter (Units

Index)

AI1/AI2 block: Scale : Units Index
To change the unit, select the desired unit from

the displayed unit list.

7.3.8 Measurement Range

The unit parameter is set at the factory before

shipment if specified at the time of order. To change

the measurement range, follow the procedure

below.

■ Procedure to call up the lower limit setting

parameter (EU at 0%)

AI1/AI2 block : Scale : EU at 0%