Table 8.3

Cause and Countermeasure

Observed Problems

Possible Cause

Countermeasure

Related Parameter

Output fluctuates greatly. Input adjustment by user was

not correctly done.

Set or clear the user adjustment

value.

• Lin Type

• Sensor Range

Damping adjustment is not

correct.

Set the damping adjustment to

0.

• Process Value Filter

Time

Transmitter outputs fixed

current.

Input adjustment by user was

not correctly done.

Set or clear the user adjustment

value.

• Lin Type

• Sensor Range

The simulation function is set

to ON.

Set the simulation function to

OFF.

• Simulate Switch

Output is reversed.

The lower limit value is greater

than the upper limit value.

Set the correct value to the

upper limit value and the lower

limit value.

• Lin Type

• Sensor Range

• Cal Point Lo

• Cal Point Hi

Parameters cannot be

changed.

The transmitter is in write

protect status.

Release write protect.

• UAP Option

• Hardware Write Protect

8.5.3 Errors and Countermeasures

Table 8.4

Error Message Summary

Integral

indicator

Factory

NAMUR

category

Bit

Diagnostic

Status

Diagnostic

Status Detail

Cause

Release/

recovery

conditions

(except

restart)

Output

Operation

Action

AL.02

AMP.

ERR

*2

F

Bit

27

Faults in

electronics

AMP ERR

Amplifier

temperature

sensor error

None

The output

is fixed to

±99999°C.

The sign is

dependent on

the burnout

switch at the

LCD board or

Burn Out Type

parameter

*4

.

Replace the

amplifier.

MEMORY

ERROR

Amplifier memory

failure

None

Same as

above

Replace the

amplifier.

ADC ERROR

Amplifier AD

converter failure

None

Same as

above

Replace the

amplifier.

AL.03

FUP.

ERR

*2

Firm Update

ERR

Firmware update

write error

None

----

Replace the

amplifier.

AL.10

S1.FAIL

*2

F

Bit

26

Faults in

sensor or

actuator

element

S E N S O R 1

FAILURE

Sensor 1 burnout

None

The output

is fixed to

±99999°C.

The sign is

dependent on

the burnout

switch at the

LCD board or

Burn Out Type

parameter

*4

.

Replace the

sensor 1.

AL.12

RJ.FAIL

*2

T E R M S N S

FAILURE

CJC sensor

burnout

None

Operable at

the CJC value

(0°C).

Replace the

CJC sensor.