<8. Maintenance>

8-9

IM 01C50E01-01EN

Integral

indicator

Factory

NAMUR

category

Bit

Diagnostic

Status

Diagnostic

Status Detail

Cause

Release/

recovery

conditions

(except

restart)

Output

Operation

Action

AL.20

LOWBAT

*3

M

Bit

19

Power is low:

maintenance

need mid-term

LOWBAT

Low remaining

battery voltage

None

Normal action

Replace the

batteries.

Bit

20

*4

Power is

critical low:

maintenance

need short -

term

CRITICAL

LOWBAT

Low remaining

battery voltage

None

Normal action

Replace the

batteries.

Bit

20

*5

Power is

critical low:

maintenance

need short -

term

LOWBAT

FOR

DEEPSLEEP

Low remaining

battery voltage

causes switching

to deep-sleep

mode.

None

Normal action,

but power

turns off

15 minutes

after alarm is

generated.

Replace the

batteries.

AL.23

FIRM.C

M

Bit

21

Fault

prediction:

Maintenance

required

FIRMWARE

CONDITION

CHECK

Firmware internal

error

None

Normal action

Restart.

AL.40

S1.OVR

O

Bit

22

Environmental

conditions

out of device

specification

SENSOR1

TEMP HI

The temperature

of sensor 1 is

higher than the

temperature

specified in the

Sensor Range

parameter.

Recovers

when the

temperature

falls within

the range.

Normal action

Check the

sensor type

setting and

connection

method.

SENSOR1

TEMP LO

The temperature

of sensor 1 is

lower than the

temperature

specified in the

Sensor Range

parameter.

Recovers

when the

temperature

rises within

the range.

Normal action

Check the

sensor type

setting and

connection

method.

AL.41

S2.OVR

*4

SENSOR2

TEMP HI

The temperature

of sensor 2 is

higher than the

temperature

specified in the

Sensor Range

parameter.

Recovers

when the

temperature

falls within

the range.

Normal action

Check the

sensor type

setting and

connection

method.

SENSOR2

TEMP LO

The temperature

of sensor 2 is

lower than the

temperature

specified in the

Sensor Range

parameter.

Recovers

when the

temperature

falls within

the range.

Normal action

Check the

sensor type

setting and

connection

method.

AL.45

AMB.

OVR

O

Bit

22

Environmental

conditions

out of device

specification

AMB TEMP

HI

The ambient

temperature

is higher than

+85°C.

Recovers

when the

temperature

falls below

+85°C.

Normal action

Check the

temperature

in the

vicinity

of the

transmitter.

AMB TEMP

LO

The ambient

temperature is

lower than -40°C.

Recovers

when the

temperature

rises above

-40°C.

Normal action

Check the

temperature

in the

vicinity

of the

transmitter.