<6. Operation>

6-4

IM 01C50E01-01EN

(a) Deep sleep

F0604.ai

(b) Ready and pause

F0605.ai

(c) Confirm connecting status

F0606.ai

(d) Join

F0607.ai

NOTE

If the transmitter searches the Field wireless

Network for long time ambient temperature

condition, sometimes error "AL.20 LOWBAT" is

displayed on the Integral Indicator. Even though

using new batteries, it can occur. It occurs

because of battery characteristics. After joining

to the Field Wireless Network, this error will be

cleared within one hour if battery has no failure.

6.5 Shutting Down the

Transmitter

When shut down the transmitter, remove the battery

pack or set the transmitter to deep sleep mode by

the device configuration tool.

NOTE

• Refer to subsection 8.4.4 “Replacing the

Battery Pack” for the battery pack removing.

• When storing the instrument with a battery

pack inserted, it is recommended to put the

instrument into deep sleep mode to conserve

battery power. For details on how to switch to

deep sleep mode, refer to subsection 7.3.14

“Switching to the Deep Sleep Mode."