3 atex certification, Atex certification -6 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 14

Advertising
background image

<2. Notes on Handling>

2-6

IM 01C50E01-01EN

Temperature

Transmitter

Battery

pack

1
2
3
4
5

1
2
3
4
5

Temperature

Transmitter

Battery

pack

Temperature Sensor (*1)

Amplifier housing code 8 and 9

Hazardous Location

Antenna

(*1)

Arrester

(*1, *2)

Temperature Sensor (*1)

(One or Two sensors)

*1: These apparatus are simple apparatus.

*2: Arrester may not be connected.

Antenna Connector

F0205.ai

[Installation Drawing]

Amplifier housing code 7

Hazardous Location

Note 4. Battery Pack

Use only YOKOGAWA battery pack

F9915MA or F9915NS.

Note 5. Special Conditions for safe use

Potential electrostatic charging hazard-

secure distance of 100mm from antenna.

Do not open when CL II, III, DIV 1,2

atmosphere is present.

2.7.3 ATEX Certification

(1) Technical Data
Caution for ATEX Intrinsically safe type.
Note 1. Model YTA Series temperature transmitters

with optional code /KS27 for potentially

explosive atmospheres:

• No. KEMA 10ATEX0163 X

• Applicable Standard:

EN 60079-0:2009, EN 60079-11:2012,

EN 60079-26:2007

• Type of Protection and Marking code:

Ex ia IIC T4 Ga

• Group: II

• Category: 1 G

• Ambient Temperature: –50°C to 70°C

• Enclosure: IP66/IP67

Note 2. Output Parameters

• Sensor input circuit (Terminals 1 to 5 )

Uo: 6.6 V

Io: 66 mA

Po: 109 mW

Co: 22 μF

Lo: 8.1 mH

• The above parameters apply when one of

the two conditions below is given:

- the total Li of the external circuit (excluding

the cable) is < 1% of the Lo value or

- the total Ci of the external circuit (excluding

the cable) is < 1% of the Co value.

• The above parameters are reduced to 50%

when both of the two conditions below are

given:

- the total Li of the external circuit (excluding

the cable) is ≥ 1% of the Lo value and

- the total Ci of the external circuit (excluding

the cable) is ≥ 1% of the Co value.

• The reduced capacitance of the external

circuit (including cable) shall not be greater

than 1μF for Group IIB and 600nF for Group

IIC

Note 3. Installation

• Installation should be in accordance with

local installation requirements. (Refer to the

Control Drawing)