5.1 Notes on Wiring

IMPORTANT

• Apply a waterproofing sealant to the threads

of the connection port. (It is recommended

that you use non-hardening sealant made of

silicon resin for waterproofing.)

• Lay wiring as far away as possible from

electrical noise sources such as large

transformers, motors and power supplies.

• Remove the wiring connection dust-caps

before wiring.

• To prevent electrical noise, the signal cable

and the power cable must not be housed in

the same conduit.

5.2 Cable Selection

A dedicated cable is used for connection between

the temperature sensor and the temperature

transmitter.
When a thermocouple is used as the temperature

sensor, a compensation wire that is appropriate for

the type of thermocouple (refer to compensating

cables for IEC584-3 thermocouples) must be used.

When a resistance temperature sensor (RTD) is

used as the temperature sensor, 2-core/3-core/4-

core cable must be used (refer to resistance

thermometer sensor IEC751). In a place where the

cable will be susceptible to the effect of noise, a

shielded cable must be used.
The terminal of the dedicated cable is a 4 mm

screw.

5.3 Cable and Terminal

Connections

F0501.ai

Figure 5.1

Input Terminal Connections

The temperature sensor is to be connected as

shown in Figures 5.2.

(B1)

(A1)

1

2

3

4

5

(–)

(+)

1

2

3

4

5

(B1)

(B1)

1

2

3

4

5

(–)

(+)

1

2

3

4

5

(+)

(A1)

(B2)

(B2)

(A2)

(A)

(B)

(B)

(B2)
(A2)

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

(–)

(+)

(B)

(A)

(B)

(B)

(B)

(A)

(A)

(A)

(B)

Thermocouple and

DC voltage

RTD and resistance

(3-wire)

Thermocouple +

RTD and resistance

(3-wire)

RTD and resistance

(2-wire)

2 input (Amplifier housing code 8 and 9)

Thermocouple and

DC voltage

RTD and resistance

(2-wire)

RTD and resistance

(3-wire)

RTD and resistance

(4-wire)

1 input

F0502.ai

Figure 5.2

YTA510 Input Terminal Wire Connection