<5. Wiring>

5-5

IM 01C50E01-01EN

CAUTION

• Use the dedicated antenna extension cable

provided by Yokogawa as accessories for

the transmitters.

• The antenna extension cable and

temperature sensor cable should not be

bundled together.

5.5.2.3 Mounting of Arrester and Wiring

Mount an arrester between the extension cables

and connect the grounding cable to the grounding

terminal of the arrester as required.

Connect the grounding cable to the grounding

terminal on the transmitter body. Class C grounding

with the grounding resistance of 10 Ω or less is

necessary. Do not share the ground with other

devices.

F0508.ai

Transmitter side

Grounding cable

Antenna side

Antenna extension cable 2

Antenna extension cable 1

Arrester

Figure 5.8

Connection of the Arrester and Antenna

Extension Cable

F0509.ai

Transmitter side

Grounding cable

Antenna side

Protect by self-bonding tape

Figure 5.9

Arrester Protection by Self-bonding

Tape

5.6 Grounding

When using the antenna extension cable with an

arrestor, Class C grounding with the grounding

resistance of 10 Ω is required. In other cases,

always ground the transmitter case in accordance

with national and local electrical codes. The most

effective transmitter case grounding method is

a direct connection to earth ground with minimal

impedance.
Grounding terminals are located inside and outside

of the terminal block respectively. Any of them may

be used.

F0510.ai

Grounding terminal

Figure 5.10 Grounding Terminal

Grounding terminal

F0511.ai

Figure 5.11 Grounding Terminal inside the Terminal

Cover