<9. Parameter Summary>

9-7

IM 01C50E01-01EN

Table 9.2

Diagnostic Status Detail

Bit

Diagnostic Status Detail

Description

Diagnostic

status

assignment

bit

NAMUR

Diagnostic Status Detail.1
Bit31

AMP ERR

Amplifier failure

Bit27

F

Bit30

MEMORY ERR

Memory failure

Bit27

F

Bit27

Firm Update ERR

Firmware write error

Bit27

F

Bit26

ADC ERR

ADC failure

Bit27

F

Bit23

SENSOR1 FAILURE

Sensor 1 burnout

Bit26

F

Bit22

SENSOR2 FAILURE

*1

Sensor 2 burnout

Bit26

F

Bit21

TERM SNS FAILURE

CJC sensor burnout

Bit26

F

Bit16

CRITICAL LOWBAT

*1

Deep sleep due to low battery

Bit20

M

Bit15

LOWBAT

Low battery

Bit19

M

Bit14

LOWBAT FOR DEEPSLEEP

*2

Deep sleep due to low battery

Bit20

M

Bit11

FIRMWARE CONDITION CHECK

Internal control error detection

Bit21

M

Diagnostic Status Detail.2
Bit31

SENSOR1 TEMP HI

Sensor 1 temperature higher limit scale out

Bit22

O

Bit30

SENSOR1 TEMP LO

Sensor 1 temperature lower limit scale out

Bit22

O

Bit29

SENSOR2 TEMP HI

*1

Sensor 2 temperature higher limit scale out

Bit22

O

Bit28

SENSOR2 TEMP LO

*1

Sensor 2 temperature lower limit scale out

Bit22

O

Bit27

AMB TEMP HI

Ambient temperature higher limit scale out

Bit22

O

Bit26

AMB TEMP LO

Ambient temperature lower limit scale out

Bit22

O

Bit23

SENSOR1 SPAN ADJ ERR

Sensor 1 faulty input of span adjustment

value

Bit25

C

Bit22

SENSOR1 ZERO ADJ ERR

Sensor 1 faulty input of zero adjustment value Bit25

C

Bit21

SENSOR2 SPAN ADJ ERR

*1

Sensor 2 faulty input of span adjustment

value

Bit25

C

Bit20

SENSOR2 ZERO ADJ ERR

*1

Sensor 2 faulty input of zero adjustment value Bit25

C

Bit15

AI1 O/S MODE

AI1 O/S Mode

Bit24

C

Bit14

AI2 O/S MODE

*1

AI2 O/S Mode

Bit24

C

Bit13

AI1 SIMULATE MODE

AI1 Simulate Mode

Bit17

C

Bit12

AI2 SIMULATE MODE

*1

AI2 Simulate Mode

Bit17

C

*1: Applicable for dual input type with detachable antenna, Amplifier housing code 8 and 9.

*2: Applicable for single input type with integral antenna, Amplifier housing code 7.

F0901.ai

AI algorithm

Filtering

PV

AI publish

Simulate

value

Sensor

Signal

SIMULATE

Linearization

INPUT_RANGE

SENSOR_CONNECTION

Linearization

SCALE

PV_FTIME

Data Publication Period

Scale

Transducer

value

EXT_RJ_VAL

RJ.

RJ_TEMP RJ_TYPE

BIAS

LIN_TYPE

Switch

Input

MODE.Target

NO REF

+

+

PV_TYPE

PV

PV

PV

MODE and

PV.Status handling

O/S

Auto

Man

Operator

Operator

Operator

Figure 9.1

Example schema of analog input object

Advertising