Yokogawa EXA PH202 2-Wire pH/ORP Analyzer User Manual

Page 17

Advertising
background image

IM 12B07D02-01E

2-4 Specification

mA-HART® communication
A. Input

: Two wire system 4-20 mA

B. Power supply

:

PH202G :

up to 40 volts

PH202S :

up to 31.5 volts

Note:

The transmitter contains a switched

power supply, drawing its energy

from the 0-4 mA section of the signal.

Consequently the 17 volt limit is

applied at 4 mA. The characteristic of

the unit is such that above about 7 mA

on the output, the terminal voltage can

drop to 14.5 volts without problem.

(see figure 2-2)

C. Transmission:

Isolated output of 4 to 20 mA DC.

D. Signal

: Maximum load 425Ω. (see fi gure 2-1)

Burn to signal failure acc.

NAMUR Recommendation NE43

(18.01.1994)

E. Operating range :

3.9 to 21mA

F. Communication

:

HART®, 1200 Baud, FSK

modulated on 4 to 20 mA signal

G. Configuration

: Local with 6 keys

H. Software :

Firmware based on Yokogawa stack.

I. Hardware :

Yokogawa HART® Modem F9197UB

J. Other Control systems

:

Yokogawa PRM, Rosemount AMS,

Siemens PDM

K. Hand Terminal :

Rosemount HHT 275/375

L. Other control systems:

Yokogawa PRM,

Rosemount AMS, Siemens PDM

M. Output span

:

- pH

: min 1 pH, max 20 pH.

(max 90% zero suppression)

: The instrument is user

programmable for linear or non-

linear pH ranges.

N. Cable specification

:

0.5 mm diameter or 24 AWG over

maximum length of 1500 m

O. DD specification

:

The PH202 Device Description is

available enabling communications

with the Handheld Communicator

and compatible devices.

mA

NEPSI Certification (PH202S-K)

NEPSI Intrinsically Safe Type

Cert No. GYJ081156X

• Applicable Standard:

GB3836.1-2000, GB3836.4-2000

• Type of Protection and Marking Code:

Ex ia IIC T4/T6

• Ambient Temperature :

T6; –10 to 40°C, T4; –10 to 55°C

Note 1 Entity Parameters

• Intrinsically safe input parameters

(terminal + and -):

Maximum Input Voltage (Ui) = 31.5 V

Maximum Input Current (Ii) = 100 mA

Maximum Input Power (Pi) = 1.2 W

Maximum Internal Capacitance (Ci) = 22 nF

Maximum Internal Inductance (Li) = 35 μH

• Intrinsically safe output parameters and

maximum external parameters

(terminal 11 and 17):

Uo=14.4 V, Io=32.3 mA, Po=0.12 W, Co=600

nF, Lo=34 mH

Note 2 Installation

• Electrostatic charges on the display window shall

be avoided.

• The external earth connection facility shall be

connected reliably.

• The instrument modification or parts replacement

by other than authorized representative of

Yokogawa Electric Corporation and will void

NEPSI Intrinsically safe certification.

• The user shall not change the configuration in

order to maintain/ensure the explosion protection

performance of the equipment. Any change may

impair safety.

• For installation, use and maintenance of

the product, the end user shall observe the

instruction manual and the following standards:

GB50257-1996 "Code for construction and

acceptance of electric device for explosion

atmospheres and fire hazard electrical

equipment installation engineering''.

GB3836.13-1997 "Electrical apparatus for

explosive gas atmospheres Part 13: Repair and

overhaul for apparatus used in explosive gas

atmospheres".

GB3836.15-2000 "Electrical apparatus for

explosive gas atmospheres- Part 15: Electrical

installations in hazardous area (other than

mines)" .

GB3836.16-2006 "Electrical apparatus for

explosive gas atmospheres- Part 16: lnspection

and maintenance of electrical installation (other

than mines)".