Pressure sensor calibration – In-Situ Aqua TROLL 100 and 200 Operators Manual User Manual

Page 63

Advertising
background image

Page 63

Aqua

TROLL Operator’s Manual

Pressure Sensor Calibration
Factory Recalibration
Pressure sensor accuracy can be adversely affected by improper

care and handling, lightning strikes and similar surges, exceeding

operating temperature and pressure limits, physical damage

or abuse, as well as normal drift in the device’s electronic

components. Aside from damage to the sensor, the need for

factory recalibration is dependent upon the amount of drift a

customer is willing to tolerate. Factory calibration every 12-18

months is recommended. Contact In-Situ Customer Service for

information on the factory maintenance and calibration plan.
Field Recalibration
The following procedure may be used, with caution, to set

to zero the offset of a vented pressure sensor to correct for

electronic drift. The drifted offset is visible when the sensor is in

air and reading other than zero.

It is recommended you do not set to zero the offset if it is

outside the specified accuracy of your pressure sensor, as shown

in the table below. If the reading in air deviates from zero by

more than the amounts shown, you may want to consider a

factory recalibration.

Sensor

Accuracy

Acceptable Offset

range

(0°C to +50°C)

from zero

5 psi

± 0.1% FS

± 0.005 psi

15 psi

± 0.1% FS

± 0.015 psi

30 psi

± 0.1% FS

± 0.03 psi

100 psi

± 0.1% FS

± 0.10 psi

300 psi

± 0.1% FS

± 0.30 psi

500 psi

± 0.1% FS

± 0.50 psi

TIP: In Level
mode, any zero
pressure offset is

corrected automatically. The
field recalibration procedure
is not necessary except when
measuring pressure.

Section 6: Pressure & Level

Advertising
This manual is related to the following products: