Foxcom (digital) summary, Mounting to the actuator (valve), Connection and startup – Badger Meter SRD/SRI Valve Positioners User Manual

Page 11: System configuration, Foxcom (digital) summary 11

Advertising
background image

FOXCOM (DIGITAL) SUMMARY

Mounting to the Actuator (Valve)

The SRD960 can be mounted to stroke or rotary actuators

Connection and Startup

Connect the pneumatic tubing Upon connection of supply air and a voltage source of, for example, 24V DC to the input

terminals (pay attention to polarity), an initial startup can be carried out without any further equipment
Use the local push-buttons to change basic parameters such as type of actuator, side of installation, valve opens/closes with

increasing setpoint value, and characteristics curve of the valve (values set ex-factory: stroke actuator, mounting side: left,

valve opens with increasing setpoint value, linear characteristics curve)
Thereafter, an AUTOSTART can be performed during which the SRD960 determines independently the geometric data of the

actuator as well as control parameter, to ensure an optimized operation with the attached valve
FoxCom Version

The positioner can be operated either locally via PC or via I/A Series System (FoxCom)

System Configuration

When using Communication (a digital signal with constant amplitude), make sure that the connected outputs, buffer

amplifier and barriers are compatible with the frequency ranges used In addition to the load, the AC impedances

requirements must be met Therefore, it is recommended that only the specified amplifier, barrier and configuration device

is used
To prevent crosstalk between lines and reduce disturbances through electromagnetic influences, it is recommended that

twisted-pair shielded lines be used, with a diameter of AWG 22…14 (0 3…2 5 mm

2

) and a maximum capacity of 100 pF/m

The line capacities and connected devices may not exceed the maximum values listed for a particular FoxCom protocol
All components connected to the SRD in an explosion-hazard area require an Ex-Approval The applicable limit values must

not be exceeded These limit values also have to be adhered to when connecting additional capacitances, inductances,

voltages and currents

Figure 5: FOXCOM

Page 11

FoxCom (Digital) Summary

August 2014

POS-UM-00009-EN-02

Advertising