Linear actuator, direct mounting, Linear actuator, direct mounting 23 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 23

Advertising
background image

Linear Actuator, Direct Mounting

Actuators with appropriately prepared yoke (PA200, PA350)

enable mounting of the SRD directly to the actuator yoke

Figure 23: Direct mounting to linear actuator

The positioner is attached by bolting it directly to the

actuator yoke using the feedback lever for a direct mount

(with attachment kit EBZG -E)
The rear output I and the side outputs I and II are used

as follows:
• Actuator single acting, spring force closes:

The rear output I is used (remove lock screw in hole D)

The side output I is closed by means of a lock screw

• Actuator single acting, spring force opens:

The side output I is used

The rear output I is closed by means of a lock screw

• Actuator double acting:

The rear output I and the side output II is used

The side output I is closed by means of a lock screw

Pneumatic connections: Do not use Teflon tape for sealant

The fine fibers could disturb the function of the SRD Use only

Loctite® #243 for sealant and apply it only to male threads
Screw-type glands for electrical connections are positioned

on the lower side Any idle female threads are closed by

means of plugs

Preparation of the Positioner
Rotate the shaft stub of shaft 9 so that the flat on the shaft

stub is perpendicular to the arrow 26 on the housing (see

“Mounting Dimensions, Direct Mounting”

) Fasten the feedback

lever A to the shaft by means of spring washer and nut M8

Figure 24: Positioner preparation

Preparation of the Actuator
Screw in the carrier bolt B on the coupling piece K on the

drive spindle S at the lower left and lock it by means of a

nut M6

M6

B

K

S

R

Figure 25: Actuator preparation

Mounting of the Positioner
Fasten the positioner to the upper part of the yoke using

2 spring washers and 2 screws M8 x 80, as shown The

rear output I of positioner has contact to the air duct R in

the yoke
Attention: Note the correct position of the O-ring on the yoke

for the rear connection I!
The carrier bolt B is in the slot of the feedback lever A and the

compensating spring F touches the carrier bolt

Figure 26: Feedback lever

Page 23

Mounting to Linear Actuators

August 2014

POS-UM-00009-EN-02

Advertising