Badger Meter SRD/SRI Valve Positioners User Manual

Page 47

Advertising
background image

Table 4: Allocation of the parameter values to coding:

In LCD shown values:

[in Menu Nr.]

Code

LEDs

1 2 3 4

P

[6.1]

P

[6.2]

Tn

[6.3]

Tn

[6.4]

(sec)

T63

[6.5]

T63

[6.6]

(sec)

Dead band

[6.7]

(%)

1

1 0 0 0

2

1

0.1

0

2

0 1 0 0

2.66

1.33

0.15

0.12

3

1 1 0 0

3.50

1.75

0.25

0.16

4

0 0 1 0

4.7

2.4

0.35

0.22

5

1 0 1 0

6.3

3.2

0.5

0.3

6

0 1 1 0

8.4

4.2

0.75

0.4

7

1 1 1 0

11.2

5.6

1.15

0.53

8

0 0 0 1

15

7.5

1.75

0.7

9

1 0 0 1

20

10

2.6

0.94

10

0 1 0 1

26.6

13.3

3.9

1.25

11

1 1 0 1

35.5

17.8

5.9

1.67

12

0 0 1 1

47.3

23.7

8.85

2.22

13

1 0 1 1

63.1

31.6

13.3

2.96

14

0 1 1 1

84.2

42.1

20

3.95

15

1 1 1 1

112.2

- off -

30

5.3

Allocation of the parameter values to coding

Remarks to Controller Tuning
If AUTOSTART does not find the optimum setting the

following may be the result:
• A) small response to setpoint, long positioning time or

long neutral time

• B) continuous oscillation following setpoint jump
• C) wide and high overshoot
For the assessment of the control 12 5% jumps in both

directions may be performed in Menu 8 The valve dynamics

may be observed at LCD or the mechanical indicator
Prior to changing parameters for valve dynamics a number

of items are to be checked, see below The pneumatic output

can be approached directly without controller via Menu 7

and the valve movement may be assessed
For behavior A) check:
1 Is the Proportionate gain P (Menu 6 1) or P  (Menu 6 2)

too small?

Remedy: Increase parameters according to chart 4

2 Is the air pressure high enough to possibly overcome

trouble-free the actuator spring force and friction

(dimensioning)?

Remedy: Increase the air pressure

3 Is the actuator volume high, possibly requiring an

increased air capacity for fast valve movement?

Remedy: Through booster, see accessories

4 Was AUTOSTART performed in Menu 2 and did messages

8 or 9 occur?

Remedy: AUTOSTART in Menu 2 or observe information

in table

5 Has the parameter for the positioning time been set at a

value too high?

Remedy: Decrease both parameters T63 in Menu 6 5 or

6 6

6 Is valve packing too tight resulting in a very high friction?
7 Is the supply air filter blocked?

Remedy: See

"Supply Filter Replacement" on page 54

8 Has the supply air been contaminated by small oil drops

or particles or are pneumatic parts possibly blocked?

Remedy: Exchange of pneumatic parts; possibly use a

suitable air supply station

For behaviors B) and C) check:
1 Has the air supply pressure been set too high?

Remedy: Reduce pressure or install pressure reducer

2 Is the proportional amplification in Menu 6 1 or 6 2 too

high? The values can possibly be at Code 15

Remedy: Reduce the amplification

3 Is the air capacity possibly too high, for instance, through

spool valve or booster?

Remedy: Work, if necessary, without booster or use

version without spool valve

Changing valve dynamics during behavior A):

If valve has a high friction (for example, often the case in

small rotary actuators due to low air supply pressure or due

to a valve seat packing which is too tight) then the valve

position gets stuck after a setpoint jump and possibly is

recontrolled via the resetting time Tn, possibly after quite

some time has elapsed

Page 47

Startup

August 2014

POS-UM-00009-EN-02

Advertising