DECOMMISSIONING

Before decommissioning the unit, disconnect the supply air

and the electrical input signal
After disconnecting the electrical input signal the last

confirmed configuration of the positioner is preserved in

the memory

Exchange of Device

If a temporary decommissioning of the SRD and a later

mounting to another actuator has to be carried out, before

disconnecting, we recommend to Reset Configuration in

Menu 9 1 So the default settings ”Ex-Factory” are reactivated

This facilitates a later recommissioning

MAINTENANCE

The SRD960 requires no periodical maintenance

When replacing components during repair work,

“Safety Requirements” on page 66

must be observed!

Service Plug and IrCom

All basic instruments of the SRD960 are equipped with

a service plug A There via RS232 a PC with PC20 / PC50

(FDT-Software) can be connected via modem EDC82 (galv

separated, not Ex)
This universal interface, together with the PC software,

allows the configuration of all SRD versions independent of

the protocol—thus versions HART, FOUNDATION Fieldbus,

PROFIBUS PA, FoxCom and also the version “without

communication” can be configured from the PC, without

having to acquire expensive modems For details see TI

to EDC82
The service plug (6 pole pin strip) is accessible from the side

after unscrewing of cover to electronic compartment The

6-pole connector links EDC82 modem with SRD, and from

EDC82 a 9 pole subD cable links to RS232 interface of PC

Figure 39: Service plug and IrCom

If the SRD is equipped with option IrCom B , communication

can take place without contact via infrared with the

positioner (even with closed cover) Modem IR Interface (not

Ex) is connected via RS232 to a PC (for practical reasons a

notebook) with software PC20 / PC50 and makes possible a

range of approximately 1 meter
(If the notebook has an IrDa interface, this cannot be used,

despite similar technique The IrDa instruction set has no

communication instructions for positioners )

Supply Filter Replacement

An obstructed supply filter can be replaced Unscrew the air

supply fitting, remove the filter and exchange the filter with

a new one

Pneumatic Amplifier

Upon unscrewing of lateral cover, the pneumatic

compartment is accessible

Figure 40: Single-acting amplifier

• Pre-Amplifier: Unscrew 4 screws K
• Amplifier: Unscrew 2 screws J
• When remounting, verify the correct seating of sealings
Damping Screws (Service Only)
The damping screws are adjusted optimal ex-factory; the

screw head is even with the amplifier surface Generally this

is the most favorable setting, without damping

Replacement of Mechanical and Pneumatic

Units

See following pages