OPERATING MODES

Operation of the positioner is divided into individual

operating modes Operating modes may change depending

on, for example, key commands or internal calculations
The different operating modes are described in abbreviated

form below

Initialize

Upon powerup or reset (pressing keys () (–) (+)

simultaneously), several self-tests are conducted Individual

steps in the self-test process are indicated by the LCD or

green LEDs
If no error occurs, the device moves to OUT OF SERVICE, if it is

still in a delivery condition; AUTOSTART has to be performed

If AUTOSTART was done already, the device will go to

IN OPERATION
If faults are detected, the code of the faulty self-test will

remain If error reoccurs after reset, the device is probably

defective and should be sent in for repair

Device Fault

In the event that the LCD shows a message (or red LED lights

up constantly and all green LEDs are off), a device fault is

signaled These faults are detected during cyclical self-test
The device can no longer be operated This could be caused

by a jammed menu key or defective program memory See

"Troubleshooting Guide" on page 60

This condition disappears through new resetting until

the same error is detected again If a device error occurs

repeatedly, the device should be sent in for repair

In Operation

After performing an AUTOSTART, the device moves to

IN OPERATION and will always, even after restarting or

resetting, move back to the safety position (de-energized

valve position) or FAILSAFE If setpoint values are fed via

communication, the SRD will go to IN OPERATION

Failsafe

Positioner carries out actions as configured in menu Failure

Handling Additionally, the cyclical self-diagnosis takes place
If the instrument is IN OPERATION, but no setpoint values

arrive via communication, the SRD will go to FAILSAFE mode,

after a defined time period; with
• Maintaining last value
• Output pressureless, or
• Predetermined position
As soon as setpoint values arrive via communication again,

the instrument is immediately back IN OPERATION

Out of Service

The SRD960 in its delivery condition is configured in such

a way that it will remain OUT OF SERVICE after powerup

until moving to IN OPERATION via the manually initiated

function AUTOSTART
In the device state OUT OF SERVICE, the menu entering mode

remains active at all times If a device has been IN OPERATION

already and is removed from an actuator and mounted to

another, take the device out of operation via RESET CONFIG

(Menu 9 1) prior to disconnecting the device from the

first actuator
This enables the next actuator to be started in the delivery

condition (see

"Startup" on page 32

)

Calibrate

During an AUTOSTART function the device state is in

CALIBRATION The actuator is moved up and down several

times, and the device could be busy for a longer period of

time Subsequently, the device moves to IN OPERATION

Message

The SRD960 continuously supervises its important device

functions In the event that limit values are exceeded or

operational problems occur, messages are signaled via the

LCD or the special LED blinking mode: red LED with long,

green LEDs with short fluorescent time
The message with the highest priority will be indicated

first With the minus key (–), additional messages can be

called up; with plus key (+), the measuring values can be

retrieved You can access the menu at any time buy pressing

the menu keys Further references may be found in chapter

"Troubleshooting Guide" on page 60

Simulate (FOUNDATION Fieldbus Version Only)

When IN OPERATION, the valve position queried via the

communication can be simulated with a value that has been

entered via communication into the instrument during

SIMULATION Thereby, the positioner continues with normal

operation and regulates to the ”accurate” set value
For the SRD , this function has to be additionally released or

blocked via menu 10
LCD description, definition of the LEDs and possible operator

interventions are described in

"Startup" on page 32

Page 14