SAFETY REQUIREMENTS

EMC and CE

For notes regarding Electromagnetic compatibility, EMC, and

CE labels see the Product Data Sheet
In order to ensure EMC protection, the screwed electronics

housing must be locked

Explosion Protection

(Only if ordered)
Technical data for explosion protection see Product Data

Sheet or Certificates of Conformity EX EVE0109 A
For installations located in explosive atmospheres, all

relevant national regulations and installation conditions

must be observed, for example, in the Federal Republic of

Germany ElexV and DIN VDE 0165

MPORTANT

I

When repairing explosion-protected equipment, observe the

national regulations.

Repairs involving parts must be manufacturer’s original parts
The following applies to the Federal Republic of Germany:

Repairs involving parts required for explosion protection

must either be carried out by the manufacturer or by

authorized personnel and confirmed by certificate

SYSTEM CONFIGURATION

The safety requirements must be observed!

HART Communication

When using the ‘communication’ (an alternating current

signal, which is modulated onto the 4…20 mA signal),

make sure that the connected outputs are suitable for

the used frequency ranges Apart from the load, also

check the alternating current impedances Use only

suitable instruments
To eliminate crosstalk between leads and to reduce

disturbances through electromagnetic influences, use

twisted paired shielded leads (0 3…2 5 mm

2

, max 100 pF/m)

The capacities of the leads and the connected instruments

must not exceed the maximum values for HART
All components that are connected to the SRD in an

explosion hazardous area, require an Ex-Approval The

applicable limit values must not be exceeded in any

case These limit values also have to be adhered to when

connecting additional capacitances, inductances, voltages

and currents
Measuring HART Communication Signal
If a reliable communication signal cannot be received, check

the level with an oscilloscope The first data block always

comes from the configurator and the second block is the

reply from the SRD

HART

measured at
configurator:

measured at

SRD:

Configurator
transmits

at least

350 mVpp

at least

120 mVpp

SRD960
transmits

at least

120 mVpp

at least

400 mVpp

FoxCom Communication

When using the ‘communication’ (a rectangular signal

which is modulated onto the constant current signal), make

sure that the connected outputs are suitable for the used

frequency ranges The supply instrument must be a voltage

source with an impedance of 250…500 Ohm The total of

all instrument and lead capacities must be <60 nF Use only

suitable instruments
To eliminate crosstalk between leads and to reduce

disturbances through electromagnetic influences, use

twisted paired shielded leads (0 3 2 5 mm

2

, max 100 pF/m)

The capacities of the leads and the connected instruments

must not exceed the maximum values for FoxCom

Page 66

Safety Requirements

August 2014

POS-UM-00009-EN-02