Open Housing

Unscrew cover safety lock

Z until

cover

C is completely free.

Then unscrew cover

C .

Tilt Electronic Forward

Unscrew the 3 screws

D , and the

round electronic

E can be tilted

forward.

Should the electronic have to be
removed completely, then unscrew
also screw

F , and pull out plug U

from the electronic.

When removing (and when re-
inserting), the correct position of
the flat cables must be observed.

Electronic

E detached.

Upon exchange of the electronic

E,

the angle calibration and an
Autostart must be performed!