Menu 6: Parameter for Position Controller

Along with the determination of the actuator geometry and control
parameters the suitable setting parameters for the position controller are
determined via function AUTO- START in Menu 2. Assessment of a
control behavior generally is very subjective. Partially a quick response is
requested without consideration of the overshoot width, partially a very
smooth swinging is requested with minor overshoot.

We basically recommend to first perform the execution of the automatic
setting via AUTOSTART in Menu 2 in order to achieve a stable control
behavior. Corrections may then be made from the determined values.
In rare cases AUTOSTART cannot find the optimal setting for the
respective application. See “Remarks for controller optimization” following
table 4.

For small actuators an improvement of the control behavior can be achie-
ved also by increasing damping at the pneumatic output. A further
optimization may follow by repeating AUTOSTART.

M

1

2

3

4

½ ½

-

½

-

M, LED 1 and LED 3 flash

Seven control parameters are combined in Menu 6 each availing of a sub-
menu. 15 different values may be selected in each of these and pressing
of ( ) be entered in the position controller as constant. Controller type is a
PI controller.

Parameter-
Designation

Valve is

opening

Valve is

closing

Unit

Proportionate
amplification

KP

P

P

-

Integration time
constant

Tn

Tn

sec

Positioning time

T63

T63

sec

Dead band for
control diff.

GAP

GAP

% of span

The dead band prevents (at the expense of accuracy) that the valve in the
controlled condition constantly moves around the setpoint. This less harms
the mechanical parts of the actuator and in particular the valve packing.

Selection of sub-menus:

M

1

2

3

4

¼

-

¾

-

-

M, LED 2 flash:

P

¼ ¾ ¾

-

-

M, LED 1 and LED 2 flash:

P

¼

-

-

¾

-

M, LED 3 flash:

Tn

¼ ¾

-

¾

-

M, LED 1 and LED 3 flash:

Tn

¼

-

-

-

¾

M, LED 4 flash:

T63

¼ ¾

-

-

¾

M, LED 1 and LED 4 flash:

T63

¼

-

¾ ¾

-

M, LED 2 and LED 3 flash:

GAP

Following selection of the sub-menu the codes for the parameter values
(table 4) can be selected by pressing ( ) :

SRD Main Menu

4 Valve Char.

5 Limits/Alarms

6 Parameters

6 Parameters

6.1 Gain closing

6.2 Gain opening

6.3 Res time cl

etc.

6 Parameters

6.4 Res time op

6.5 Rate lim cl

6.6 Rate lim op

6 Parameters

6.5 Rate lim cl

6.6 Rate lim op

6.7 Control gap