Namur mounting, right hand, Namur mounting, right hand 21 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 21

Advertising
background image

NAMUR Mounting, Right Hand

Right-hand mounting is done if, for instance, left-hand

mounting is not possible for structural reasons
Applicable to actuators with cast yoke or pillar yoke

according to NAMUR (DIN IEC 534-6)
Mounting the positioner with pneumatic connections on the

right side and electrical connections on the lower left side

Figure 18: NAMUR mounting, right hand

Attachment of the positioner to the actuator is made to the

right using the mounting bracket and feedback lever for a

NAMUR mount Use:

• Attachment kit EBZG -H for a cast yoke, or

• Attachment kit EBZG -K for a pillar yoke

The side outputs I (or I and II) are used The rear output I is

closed by means of a lock screw 522 588 013
Pneumatic connections: Do not use Teflon tape for sealant

The fine fibers could disturb the function of the SRD Use only

Loctite® #243 for sealant and apply it only to the male thread
Screw-type glands for electrical connections are positioned

on the lower side Any unused threaded holes are plugged
Preparation of the Positioner
Rotate the shaft stub of shaft 9 so that the flat on the shaft

stub is perpendicular to the arrow 26 on the housing (detail,

“NAMUR Mounting Dimensions, Right Hand” on page 22

)

Fasten the feedback lever A to the shaft by means of spring

washer and nut M8

Figure 19: Positioner preparation

Preparation of the Actuator
Screw the carrier bolt to the stem connector and lock it by

means of a counter nut
A carrier bolt with an adjustable length is used to be able to

screw on various coupling pieces

Figure 20: Actuator preparation

It consists of a stud S, which is screwed into the coupling

piece K (with 3 mm Allen key) and locked with a lock nut

M6 The threaded sleeve H is screwed onto it and locked

with a lock nut M6 Make sure that the bolt is adjusted to the

right length!
Fasten the mounting bracket to the right side of the yoke

For a cast yoke, use a screw M8 x 30; for a pillar yoke, use two

U-bolts and two nuts
Mounting of the Positioner

Fasten the positioner to the mounting bracket using two

spring washers and two screws M8 x 80
The carrier bolt B is in the slot of the feedback lever A and the

compensating spring F touches the carrier bolt

Figure 21: Positioner mounting

For optimum use of the positioner operating range, adjust

the arrangement according to the following procedure

before fixing At an actuator position in the middle of travel

range, the feedback lever position should be perpendicular

to the actuator stem and the angle range should be between

−10…10° and −45…45°
Fasten the positioner to the mounting bracket so that a

suitable angle range is selected Make the pneumatic and

electrical connections after adjusting the position

Page 21

Mounting to Linear Actuators

August 2014

POS-UM-00009-EN-02

Advertising