Option—premium diagnostic, item 3, Option—premium diagnostic, item 3 31, Mportant i – Badger Meter SRD/SRI Valve Positioners User Manual

Page 31: Option—premium diagnostic, Item 3

Advertising
background image

Code Q – Position Feedback and Alarm, Item 1

The analog output for position feedback indicates the valve

position 0…100% as current signal 4…20 mA

1)

Signal range

3 8…20 5 mA, at fault approximately 0 5 mA
The binary output for Alarm will be activated in the following

cases (see

"Messages" on page 61

):

• Calibration error

(for example due to break-up of calibration) Message 3

• Output outside of limits determined during Autostart

(Check mounting of feedback lever) Message 5

• Circuit to potentiometer is disturbed

(cable plugged?) Message 5

• Circuit to IP module is disturbed

(cable plugged?) Message 6

• No actuator movement; Message 7
• Remaining control deviation (packing is too tight?)

Message 11

Signal range: 1 mA or 4…6 mA, at fault < 50 μA
During disturbance of the electronics of the SRD,

the Watchdog circuit is activated The binary output

for alarm signalizes this as “cable failure” See

"Additional Inputs / Outputs" on page 30

Code P – Two Binary Outputs, Item 1

Both binary outputs AB1 and AB2 switch to high current as

soon as the valve position is below or exceeds the associated

limit value If the binary outputs AB1 or AB2 are to be

inverted (higher current no alarm, lower current alarm),

the association upper/ lower alarm have to be exchanged,

see DTM
Signal range 1 mA or 5…6 mA, at fault < 50 μA For

installation, see

"Additional Inputs / Outputs" on page 30

Code B – Binary Inputs, Item 1

The binary inputs EB1 and EB2 for two external switches or

sensors initiate the following actions:

2)

EB1

EB2

Action

2)

closed

closed

IN SERVICE

open

closed

Position to be operated full power to 0%

closed

open

Position to be operated full power to 100%

open

open

Hold last value

1)

The direction of action of the position response message is set: valve position 0% = 4

mA; valve position 100% = 20 mA

2) Factory setting Via communication actions may be turned off or used otherwise EB1

and EB2 can thus also be used as diagnostics inputs

An input not used is to be short-circuited (wire bridge

between + and –)

MPORTANT

I

Even if opening limit or closing limit are set: these actions are

superimposed, and the actuator actually moves to 0% or 100%.

See

"Additional Inputs / Outputs" on page 30.

By DTM, the two input channels are configured so that, for

example, they can trigger a PST Start or can set a status

bit for communication purposes See instructions on the

DTM screen
Code E – B3inary In- / Outputs, Item 1

By DTM, each of both channels can be individually

configured as input or output for binary signals
Configured as input, applies the same behavior as described

in Code B
Configured as output, there can be selected:
• Signal level (NAMUR or binary 0 / 40 mA)
• Logic active high or active low current
• Enable the output due to events (PST result, alarms, and

so on; extensive selection lists—see the DTM screen )

See

"Additional Inputs / Outputs" on page 30.

Option—Premium Diagnostic,

Item 3

With pressure sensors for monitoring of supply air,

Y1 and Y2 via communication, also for PST See

“Option—Pressure Sensors”

Figure 36: Premium diagnostic

Page 31

Options

August 2014

POS-UM-00009-EN-02

Advertising