MOUNTING TO LINEAR

ACTUATORS

NAMUR Mounting, Left Hand

Applicable to actuators with cast yoke or pillar yoke according

to NAMUR (DIN IEC 534-6)
Mounting the positioner with pneumatic connections on the

left side and electrical connections on the lower right side

Figure 13: NAMUR mounting

Attach the positioner to the actuator at the left using the

mounting bracket and feedback lever for a NAMUR mount

Use:
• Attachment kit EBZG -H for a cast yoke, or
• Attachment kit EBZG -K for a pillar yoke
The side outputs I (or I and II) are used The rear output I is

closed by means of a lock screw 522 588 013
Pneumatic connections: Do not use Teflon tape for sealant

The fine fibers could disturb the function of the SRD Use only

Loctite® #243 for sealant and apply it only to male thread
Screw-type glands for electrical connections are positioned on

the lower or right side Any unused threaded holes are closed

by plugs
Preparation of the Positioner
Rotate the shaft 9 so that the flat on the shaft stub is

perpendicular to the arrow 26 on the housing (for details, see

“NAMUR Mounting Dimensions, Left Hand” on page 20

)

Fasten the feedback lever A to the shaft by means of spring

washer and nut M8

Figure 14: Positioner preparation

Preparation of the Actuator
Screw the carrier bolt to the stem connector and lock it by

means of a counter nut
A carrier bolt with an adjustable length is used to be able to

screw on various coupling pieces

Figure 15: Actuator preparation

It consists of a stud S, which is screwed into the coupling

piece K (with 3 mm Allen key) and locked with a lock nut

M6 The threaded sleeve H is screwed onto it and locked

with a lock nut M6 Make sure that the bolt is adjusted to the

right length!
Fasten the mounting bracket to the right side of the yoke
For a cast yoke, use a screw M8 x 30; for a pillar yoke, use two

U-bolts and two nuts
Mounting of the Positioner
Fasten the positioner to the mounting bracket using two

spring washers and two screws M8 x 80
The carrier bolt B is in the slot of the feedback lever A and the

compensating spring F touches the carrier bolt

Figure 16: Positioner mounting

Adjust the arrangement according to the following

procedure before fixing At an actuator position in the

middle of travel range, the feedback lever position should

be perpendicular to the actuator stem and the angle range

should be between −10…10° and −45…45°
Fasten the positioner to the mounting bracket so that a

suitable angle range is selected Make the pneumatic and

electrical connections after adjusting the position