TROUBLESHOOTING GUIDE

The components of the positioner are under constant

surveillance by the installed micro controller Errors detected

are displayed in LCD or indicated by the LEDs
Certain conditions (such as “Stroke limitation active”) are

displayed in LCD or indicated by the LEDs as message

Errors Detected During Initialization

After startup or reset, several initialization phases are passed

through which are shown in LCD or in the green LEDs If this

phase stops an error was detected
If after renewed reset

1)

the indicator stops at error code,

the device is probably defective and should be sent to the

manufacturer for repair Stating the error code will help the

Repair and Service Dept

1) Execute reset by simultaneous pressing () (–) (+) keys, or by turn-off and restart of

input signal

LED Error Codes (with LCD in true text)

LEDs

Description

red

green

M

1

2

3

4

-

1

1

1

1 Micro controller functional test

-

1

1

1

- Micro controller RAM test

-

1

1

-

1 Micro controller ROM test

-

1

1

-

- initialize operating system

-

1

-

1

1 initialize monitor

-

1

-

1

- initialize interfaces

-

1

-

-

1 initialize timer

-

1

-

-

- initialize EEPROM

-

-

1

1

1 initialize data

-

-

1

1

- initialize ADC

-

-

1

-

1 initialize communication

-

-

1

-

- initialize local operation

-

-

-

1

1 start background process

-

-

-

1

- check options and start

-

-

-

-

1 start operating system

1 = LED constant light

LED indication for diagnosis, errors:
The following combinations are possible:

After start / reset: (X X X X = error code)
M 1 2 3 4

- X X X X Error detected during Init

s. 11.1

Device in normal operation:
M 1 2 3 4
1 -

-

-

-

Cyclical self-test detects errors

s. 11.2

-

-

-

-

-

diagnosis without LED inform

s. 11.3

¾ x x x x flashing: message

s. 11.4

Errors Detected During Self-Test

During cyclical self-test, certain components of the SRD are

under constant surveillance If necessary, trouble detection

is initiated in the electronics LCD or the red LED; output y1

becomes pressureless (‘fail safe position’)
If after reset

1)

the display shows the error again the device

is probably defective and should be sent to manufacturer

for repair

LEDs

Description

red

green

M

1

2

3

4

1

-

-

-

-

Red LED lights up const.

RAM / EPROM fault

Actuate “Reset”; send device-

to manufacturer if error re-
appears

1 = LED constant light

1) Execute reset by simultaneous pressing () (–) (+) keys, or by turn-off and restart of

input signal

Page 60

Troubleshooting Guide

August 2014

POS-UM-00009-EN-02