Fault

Possible Cause

Solution

Unstable behavior,

position control circuit

oscillates

Autostart incomplete,

therefore, control

parameters not suitable

Perform a complete Autostart, see

“Menu 2: Autostart”

Small actuator volume but

high air capacity

Increase damping at pneumatic output, see

“Menu 8: Manual Setting of Valve Position”

Friction on valve packing

too great

Loosen packing gland slightly or replace

IP module or Pneumatic

amplifier defective

Change module

Actuator reacts too

sluggish

Air capacity insufficient

Attach booster

Damping set too high

Reduce damping at pneumatic output, see

“Menu 8: Manual Setting of Valve Position”

Positioning time T63 set too

high

Reduce positioning time, see

“Menu 6: Parameter for Position Controller”

No communication

possible

Input voltage too low

Eliminate voltage drop

Faulty protocol,

communicator and device

type do not match

Check configuration of devices

Wrong electronics unit

Change device

For tuning controller parameters, see

“Menu 6: Parameter for Position Controller”