System configuration, System configuration 68 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 68

Advertising
background image

System Configuration

Operating current

~ 9 mA x DC 24 V

Electrical classification

Type of protection ATEX „EEx d – Flameproof“

II 2 G EEx d IIC Temperature classes T4...T6

(Design AD 639)

EC Approval document No. PTB 02 ATEX 1084 X

Ambient temperature ranges:

Temperature class T4

–30 °C... +80 °C

(–22 °F ... 176 °F)

Temperature class T4 (on request) –40 °C ... +80 °C

(–40 °F ... 176 °F)

Temperature class T6

–30 °C... +75 °C

(–22 °F ... 167 °F)

Temperature class T6 (on request) –40 °C ... +75 °C

(–40 °F ... 167 °F)

Type of protection FM “explosion proof”

Class I Division 1, Groups B, C, D

hazardous locations, indoor and outdoor, NEMA 4X

For connections in explosion protected hazardous areas

according to directive 94/9/EG appendix II, with the follow-

ing maximum values.

Electrical connection

Connection compartment see “ELECTRICAL CONNECTION”

Electrical connection for SRD960 in non intrinsic safe

and flameproof (EEX d) version

Terminals:

Input

Options

11

12

A

B

C

D

Input signal / Setpoint value
HART/FoxCom/

4-20mA

11+ 12–

Fieldbus

acc. to IEC 1158-2

11** 12**

Options / Additonal In-/Outputs
Position

feedback

81+ 82– 31+ 32–

Binary output

81+ 82– 83+ 84–

Binary input

13+ 14– 15+ 16–

Limit signal switch

41+ 42– 51+ 52–

Potentiometer
Sensor

** any Polarity

Connection values

HART / 4-20 mA

Terminals

11+ / 12-

Signal range

4 ... 20 mA

Input voltage

DC 12 ... 36 V (non loaded)

FOUNDATION Fieldbus

Terminals

11 / 12**

Bus connection

Fieldbus interface acc. to

IEC 1158-2

Supply voltage

DC 9 ... 32 V

2)

max. Supply voltage

DC 36V

Operating current

10.5 mA ± 0.5 mA

PROFIBUS-PA

Terminals

11 / 12**

Bus connection

Fieldbus interface acc. to

IEC 1158-2

Supply voltage

DC 9 ... 32 V

2)

max. Supply voltage

DC 36V

Operating current

10.5 mA ± 0.5 mA

FoxCom

Terminals

11+ / 12-

Supply voltage

DC 13 ... 36 V

2)

max. Supply voltage

DC 36V

2) When in use in Ex-hazardous areas, the max. supply voltages, etc.

on nameplate resp. certificate of conformity, have to be observed!

Page 68

System Configuration

August 2014

POS-UM-00009-EN-02