PNEUMATIC CONNECTIONS

Figure 31: Type of thread

After aligning and mounting the positioner to the valve, connect

the pneumatic tubing
Check before mounting fittings and cable glands if threads are

matching, otherwise housing can be damaged The type of

thread is marked at housing

The applicable connection illustrations depend on the version

s

Supply air

y1-d Output 1 for direct mounting, depressurized at

currentless electronics. When using this output

y1

has to be closed by means of hex. screw.

y1 Output 1, depressurized at currentless electronics.

When using this output,

y1-d has to be closed by

means of sealing screw and O-ring.

y2 Output 2 for double-acting actuator. Full pressure at

currentless electronics. Closed at single-acting
actuator.

n1 Hex. Screw with NPT thread

Part No. 522 588 013 (stainless steel)
Part No. 556 446 016 (plastic)

n2 Sealing screw with O-ring

Figure 32: Mounting versions

Unused pneumatic connections must be closed off