With communication profibus-pa, With communication foundation fieldbus – Badger Meter SRD/SRI Valve Positioners User Manual

Page 67

Advertising
background image

All components that are connected to the SRD in an

explosion hazardous area, require an Ex-Approval The

applicable limit values must not be exceeded in any

case These limit values also have to be adhered to when

connecting additional capacitances, inductances, voltages

and currents
Measuring FoxCom Communication Signal
If a reliable communication signal cannot be received, check

the level with an oscilloscope The first data block always

comes from the configurator and the second block is the

reply from the SRD

FOXCOM

measured at
configurator:

measured at

SRD:

Configurator trans-
mits (Request)

at least

350 mVpp

at least

75 mVpp

SRD transmits
(Acknowledge)

at least

75 mVpp

at least

350 mVpp

With Communication PROFIBUS-PA

The operation of the positioner is digital, as per PROFIBUS-PA

Profile Class B according to EN 50170 and DIN 19245 part 4

Data transmission via bit synchronous current modulation

with a speed of 31250 bits via twisted and shielded two-

wire connections according to IEC 1158-2, with cable

shields on both sides and bus terminators according to

recommendation IEC 1158-2
The positioner has to be connected to a segment coupler,

which has to be conforming to IEC 1158-2 For operation

in explosion hazardous areas, a segment coupler in

explosion proof version has to be used Supply as well as

communication takes place via the bus
All components which are connected to the SRD in an

explosion hazardous area, require an Ex-Approval The

therein applicable limit values must not be exceeded in any

event These limit values also have to be adhered to when

connecting additional capacitances, inductances, voltages

and currents The FISCO model is thereby used as a basis
Further information for observance:

”Technical Guide for PROFIBUS-Connection Technique”

PROFIBUS-User Organisation, Order no 2 141

With Communication FOUNDATION Fieldbus

The operation of the positioner is digital, as per FOUNDATION

Fieldbus Specification Rev 1 4 Data transmission via bit

synchronous current modulation with a speed of 31250 bits

of via twisted and shielded two-wire connections according

to IEC 1158-2, with cable shields on both sides and bus

terminators according to recommendation IEC 1158-2
The positioner has to be connected to components which

are conforming to IEC 1158-2 For operation in explosion

hazardous areas, an Ex-separator has to be used Supply as

well as communication takes place via the bus
All components which are connected to the SRD in an

explosion hazardous area, require an Ex-Approval The

therein applicable limit values must not be exceeded in any

event These limit values also have to be adhered to when

connecting additional capacitances, inductances, voltages

and currents The FISCO model is thereby used as a basis
Further information for observance:

“Wiring and Installation 31 25 kBit/s, Voltage Mode, Wire

Medium Application Guide” by FOUNDATION fieldbus

Page 67

System Configuration

August 2014

POS-UM-00009-EN-02