Badger Meter SRD/SRI Valve Positioners User Manual

Page 48

Advertising
background image

Basically, the following is possible:
• a) To accept a remaining deviation
• b) To accept some response procedures (such as

remaining in over-response for a short time, and

remaining below setpoint and trailing)

When deciding a), Tn should become ineffective, table value

(15) Compensating P(kp) should be increased until the

setpoint jumps reach the setpoint within a short period of

time and without significant over-response (adapt to both

movement directions)
When deciding b) start as in a) above Thereafter Tn is

reswitched and decreased until the setpoint deviation has

been re-controlled within a short period of time and without

long after-response (adapt in both movement directions)

It is recommended to maintain the Tn’s for both directions

about the same
If a post oscillation occurs after a setpoint jump, Tn is selected

too small, possibly P(kp) was selected too large

The positioning time T63, also called valve damping, does

not have an effect during AUTOSTART in Menu 2, however,

setpoint jumps in Menu 8 reach the position controller in

a damped condition which then is not easily stimulated to

oscillation This behavior is also true for the setpoint input

This enables setting the controller to higher P(kp) values

without producing oscillations in the process On one side

this helps the position control to level disturbances due to

friction, changes in load or air supply pressure changes faster

On the other hand, it helps the superimposed valve control

circuit that neutral times in the valve control route do not

have such a big effect (stability in valve control circuit)
Changing valve dynamics during behavior B):

Increase Tn for both movement directions, possibly turn off

and proceed as described in behavior A) alternative b)

Page 48

Startup

August 2014

POS-UM-00009-EN-02

Advertising