Angle calibration, Angle calibration 59 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 59

Advertising
background image

Angle Calibration

When the electronic unit or the position feedback unit

is replaced, the position sensor requires calibration To

accomplish the calibration, an angle calibration tool ‘ACT’

(WKX 425 014 038) is required

Figure 41: Angle calibration tool ('ACT')

Rotate the feedback shaft 9 so that the flat side on the shaft

is perpendicular to the arrow 26 on the housing Attach the

ACT to the top of the feedback shaft Rotate the feedback

shaft counter-clockwise until the two pins line up with

the mounting holes AA on the back of the positioner, as

shown below

Figure 42: Position −45°

Push down the ACT until the pins are centered in the

mounting holes AA and fasten screws to secure the ACT to

the feedback shaft The position is now locked at – 45°
Now the measurement value of the position sensor must be

stored in the SRD This can be done locally or via software

For operation with local keys, the menu item 9 4 Calibrate

position measuring value to –45° is used Confirm with

pressing the () key
For calibration with software via PC20 / PC50 (FDT-Software)

follow the directions in the appropriate workshop function

Enter value “–45" and confirm
Now loosen the ACT and turn it with feedback shaft

clockwise 90 degrees to the second set of mounting holes

BB See

Figure 43

Figure 43: Position +45°

Push down the ACT until the pins are centered in the

mounting holes BB and screws on to secure the ACT to the

feedback shaft The position is now locked at +45°
Now the measurement value of the position sensor must be

stored in the SRD This can be done locally or via software

For operation with local keys, the menu item 9 5 Calibrate

position measuring value to +45° is used Confirm by pressing

the () key
For calibration with software via PC20 / PC50 (FDT-Software)

follow the directions in the appropriate workshop function

Enter value “+45" and confirm
Remove the angle calibrator
Reconnect the SRD at the actuator and perform an

AUTOSTART, if necessary for configuration

Page 59

Maintenance

August 2014

POS-UM-00009-EN-02