Startup, General, Startup 32 – Badger Meter SRD/SRI Valve Positioners User Manual
Page 32: General 32, Mportant i
STARTUP
General
Check the nameplate, especially with respect to indications
referring to Ex / non- Ex, input signal, communication, output
signal, single / double acting, additional inputs / outputs
Before starting the positioner, mount the SRD to the actuator;
a corresponding input signal must be adjacent and air supply
must be connected The supply air connection must have
sufficient capacity and pressure of 1 4…6 bar (20…90 psig)
and should not exceed the maximum operating pressure of
the actuator
MPORTANT
I
Configuration using local keys or the communication interface
may interfere with operation of the actual process ! During
configuration it is recommended that there is no flow through
the valve.
For initial (INIT) startup, see next page
Key Cover (Optional)
After loosening of screw A , the cover B can be turned aside
and the 4 local keys are accessible
MENU
DOWN
UP
ENTER
Figure 37: Local keys
Setting by Means of Local Keys
The SRD960 can be adjusted by means of local keys
(accessible from the outside) The keys have the
following functions:
() start menu / end menu
(–) counting down of menu or parameter numbers
(+) counting up of menu or parameter numbers
() confirm at start, or when entering, storing, or verifying
() (–) (+) simultaneously:
Reset = new start of SRD, thereafter initialization
Indication with LCD
In true text:
SRD Main Menu
1 Mounting
2 Autostart
3 Valve Action
If there is no response using the local key-pad (message
1 appears) make sure that the Write Protection is
not set! Remove the write protection using the
configuration software
DO NOT TOUCH BEHIND THE POSITIONER HOUSING
WHILE OPERATING THE KEYS! DANGER OF INJURIES!
Indication with LEDs
The LEDs serve as indication in the following methods:
M
1
2
3
4
½ ½
-
-
-
M and LED 1 flash
1
constant light, ON
¼ flashing: short ON, long OFF
½ flashing: ON and OFF same duration
¾ flashing: long ON, short OFF
–
OFF
Page 32
Startup
August 2014
POS-UM-00009-EN-02