STARTUP

General

Check the nameplate, especially with respect to indications

referring to Ex / non- Ex, input signal, communication, output

signal, single / double acting, additional inputs / outputs
Before starting the positioner, mount the SRD to the actuator;

a corresponding input signal must be adjacent and air supply

must be connected The supply air connection must have

sufficient capacity and pressure of 1 4…6 bar (20…90 psig)

and should not exceed the maximum operating pressure of

the actuator

MPORTANT

I

Configuration using local keys or the communication interface

may interfere with operation of the actual process ! During

configuration it is recommended that there is no flow through

the valve.

For initial (INIT) startup, see next page
Key Cover (Optional)
After loosening of screw A , the cover B can be turned aside

and the 4 local keys are accessible

MENU

DOWN

UP

ENTER

Figure 37: Local keys

Setting by Means of Local Keys
The SRD960 can be adjusted by means of local keys

(accessible from the outside) The keys have the

following functions:
() start menu / end menu

(–) counting down of menu or parameter numbers

(+) counting up of menu or parameter numbers

() confirm at start, or when entering, storing, or verifying

() (–) (+) simultaneously:

Reset = new start of SRD, thereafter initialization
Indication with LCD
In true text:

SRD Main Menu

1 Mounting

2 Autostart

3 Valve Action

If there is no response using the local key-pad (message

1 appears) make sure that the Write Protection is

not set! Remove the write protection using the

configuration software

DO NOT TOUCH BEHIND THE POSITIONER HOUSING

WHILE OPERATING THE KEYS! DANGER OF INJURIES!

Indication with LEDs
The LEDs serve as indication in the following methods:

M

1

2

3

4

½ ½

-

-

-

M and LED 1 flash

1

constant light, ON

¼ flashing: short ON, long OFF
½ flashing: ON and OFF same duration
¾ flashing: long ON, short OFF

OFF

Page 32

Startup

August 2014

POS-UM-00009-EN-02