P509 interface, P510 bus interface auxiliary setpoint, P513 telegram time-out – NORD Drivesystems BU0020 User Manual

Page 56

Advertising
background image

PROFIBUS DP

– Supplementary manual options for NORD - Frequency Inverters

56

BU 0020 GB-2612

P509

Interface

(Interface)

0 ... 21

{ 0 }

Selection of the interface via which the FI is controlled.

0 = Control terminals or keyboard control ** with the ControlBox (if P510=0), the

ParameterBox (not ext. P-box) or via BUS I/O Bits.

1 = Only control terminals , the FI can only be controlled via the digital and analog

inputs or via the bus I/O Bits.

8 = Profibus setpoint, the frequency setpoint is transferred via Profibus. Control via the

digital inputs is still active.

9 = Profibus control word, the control signals (enable, direction of rotation, ...) are

transferred via Profibus, the setpoint via the analog input or the fixed frequencies.

10 =

Profibus, all control data is transferred via Profibus. The analog input and the digital
inputs have no function (except safety functions)

*) Keyboard control (ControlBox, ParameterBox, PotentiometerBox) is blocked,

parameterisation is still possible.

**) If the communication during keyboard control is interrupted (time out 0.5 sec),

the FI will block without an error message.

Pos: 77 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P510

– Schnittstelle Busnebensollwerte [SK 700E] @ 1\mod_1335780555886_388.docx @ 24850 @ @ 1

P510

Bus interface auxiliary setpoint

(Bus interface auxiliary setpoints)

SK 700E/

SK750E

S

0 ... 8

{ all 0 }

Selection of the interface via which the FI is controlled.

0 = Auto (=P509): The source of the auxiliary setpoint is automatically derived from the

setting in the parameter P509 >Interface<

1 = USS

2 = CANbus

3 = Profibus

4 = InterBus

5 = CANopen

6 = DeviceNet

7 = Reserved

8 = CAN Broadcast

Pos: 78 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P513

– Telegrammausfallzeit @ 0\mod_1328092407709_388.docx @ 11180 @ @ 1

P513

Telegram time-out

(Telegram time out)

S

-0.1 / 0.0 /
0.1 ... 1000 s

{ 0.0 }

Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one
must arrive within the set period. Otherwise the FI reports an error and switches off with the error
message E010 >Bus Time Out<.

0.0 = Off: Monitoring is switched off.

-0.1 = No error: Even if communication between BusBox and FI is interrupted (e.g. 24V error,

Box removed, etc.), the FI will continue to operate unchanged.

Pos: 79 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P543

– Bus-Istwert 1 [SK 300E, SK 7x0E] @ 1\mod_1335781763553_388.docx @ 24880 @ @ 1