PROFIBUS DP

– Supplementary manual options for NORD - Frequency Inverters

80

BU 0020 GB-2612

7.3.7 Actual value 1 (IW1)

The actual value 1, i.e. the actual output frequency of the inverter, is transferred as a 16 Bit value as
standard in the actual value 1. The actual value 1 is transferred to the master in the inverter response
telegram as the second word in the process data area.

PZD1

PZD2

PZD3

PZD4

ZSW

IW1

IW2/3

IW2/3

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

The actual value 1 is transferred as a whole number in the range -32768 to 32767. In addition to the
actual frequency, other actual inverter values can be transferred. The setting is made in P543 'Actual
value 1 function
'.

The settings „Actual frequency‟, „Actual speed‟, „Current‟ and „Torque current‟ are transferred as
percentages of the respective nominal sizes. The value 16384 (4000 HEX) corresponds to 100%. The
value C000 HEX corresponds to -100%. Actual values in the range

–200% to +200% can be

transferred.

With the setting „Digital I/O status‟, the states of the control terminals and the relay (MFR) /digital
outputs can be transferred:

SK 300E/700E/750E

Bit

Status

Bits 0-5

Digital input 1-6

Bit 6-11 for POSICON special extension unit

Digital input 7-12

Bit 6 for encoder special extension unit

Digital input 7

Bits 12-15

Multifunctional relay 1-4

SK 5xxE

Bit

Status

Bits 0-4

Digital input 1-5

Bit 5-6 (above SK 520E)

Digital input 6-7

Bits 12-15

Relay and digital outputs 1 - 4

With the settings „Actual position‟ and „Setpoint position‟, the actual absolute position is transferred.
The resolution is 1 = 0.001 revolutions.

If with SK 700/750E the value 'Setpoint position 32Bit' is set in parameter P546 'Setpoint 1 function',
the actual value of the setpoint position or actual position is also transferred as a 32Bit value in PZD2
and PZD3:

PZD1

PZD2

PZD3

PZD4

ZSW

IW1

IW2

Pos: 133 /Anleitungen/Bussysteme/6. Datenübertragung/Istwert 2 und 3 (IW2/3) @ 1\mod_1336391763600_388.docx @ 25615 @ 355 @ 1