PROFIBUS DP

– Supplementary manual options for NORD - Frequency Inverters

64

BU 0020 GB-2612

P510

[-01]

[-02]

Setpoint source

(Setpoint source)

S

0 ... 10

{ all 0 }

Selection of the setpoint source to be parameterised.

[-01] = Main setpoint source

[-02] = Auxiliary setpoint source

Selection of the interface via which the FI receives the setpoint.

0 = Auto (=P509): The source of the auxiliary setpoint is

automatically derived from the setting in the parameter
P509 >Interface<

1 = Control terminals, digital and analog inputs control

the frequency, including fixed frequencies

2 = USS (or Modbus RTU SK 540E and above)

3 = CAN

4 = Profibus

5 = InterBus

6 = CANopen

7 = DeviceNet

8 = Ethernet TU

9 = CAN Broadcast

10 = CANopen Broadcast

Pos: 103 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P513

– Telegrammausfallzeit @ 0\mod_1328092407709_388.docx @ 11180 @ @ 1

P513

Telegram time-out

(Telegram time out)

S

-0.1 / 0.0 /
0.1 ... 1000 s

{ 0.0 }

Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one
must arrive within the set period. Otherwise the FI reports an error and switches off with the error
message E010 >Bus Time Out<.

0.0 = Off: Monitoring is switched off.

-0.1 = No error: Even if communication between BusBox and FI is interrupted (e.g. 24V error,

Box removed, etc.), the FI will continue to operate unchanged.

Pos: 104 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P543

– Bus-Istwert 1 [bis SK 535E] @ 0\mod_1328097541755_388.docx @ 11824 @ @ 1

P543

Bus actual value 1

(Actual bus value 1)

up to SK 535E

S

P

0 ... 24

{ 1 }

The return value 1 can be selected for bus actuation in this parameter.

The possible analog functions can be found in the following table.

NOTE:

Further details can be found in the respective BUS operating instructions or in the

description of P418.

Pos: 105 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P543

– Bus-Istwerte [ab SK 540E] @ 0\mod_1328097636349_388.docx @ 11847 @ @ 1

P543

[-01]

...

[-05]

Bus actual value

(Actual bus values)

SK 540E and

above

S

P

0 ... 57

{ [-01] = 1 }
{ [-02] = 4 }
{ [-03] = 9 }
{ [-04] = 0 }
{ [-05] = 0 }

In this parameter the return value for bus actuation can be selected.

NOTE:

The actual values 4 and 5 must be supported by the relevant bus module. Further
details can be found in the respective BUS operating instructions or in the
description of P418.

[-01] = Bus - Actual value 1

[-02] = Bus - Actual value 2

[-03] = Bus - Actual value 3

[-04] = Bus - Actual value 4

[-05] = Bus - Actual value 5