P546, Function bus setpoint, P547 func. bus-set point 2 – NORD Drivesystems BU0020 User Manual

Page 66: P548 func. bus-set point 3

Advertising
background image

PROFIBUS DP

– Supplementary manual options for NORD - Frequency Inverters

66

BU 0020 GB-2612

P546

[-01]

...

[-05]

Function Bus setpoint

(Function bus - setpoints)

SK 540E and

above

S

P

0 ... 57

{ [-01] = 1 }

all other { 0 }

In this parameter, during bus actuation a function is allocated to the setpoint provided.

NOTE:

The setpoints 4 and 5 must be supported by the relevant bus module. Further
details can be found in the respective BUS operating instructions or in the
description of P400.

[-01] = Bus setpoint 1

[-02] = Bus setpoint 2

[-03] = Bus setpoint 3

[-04] = Bus setpoint 4

[-05] = Bus setpoint 5

0 =

Off

16 = Process controller lead

1 =

Setpoint frequency

17 = BusIO In Bits 0...7

2 =

Torque current limit (P112)

18 = Curve travel calculator

3 =

Actual frequency PID

19 = Set relays, "Output status"

(P434/441/450/455=38)

4 =

Frequency addition

20 = Set analog output (P418=31)

5 =

Frequency subtraction

21 = ... 45 reserved from SK 530E and above

BU 0510

6 =

Current limit (P536)

46 = Setval.torque p.reg., "Setpoint torque

process controller"

7 =

Maximum frequency (P105)

47 = reserved from SK 530E and above

BU

0510

8 =

Actual PID frequency limited

48 = Motor temperature (SK 540E and above)

9 =

Actual PID frequency monitored

49 = reserved from SK 540E and above

BU

0510

10 = Torque servo mode (P300)

53 = d-correction F process (SK 540E and

above)

11 = Torque precontrol (P214)

54 = d-correction Torque (SK 540E and above)

12 = Reserved

55 = d-correction F+torque (SK 540E and

above)

13 = Multiplication

56 = reserved from SK 540E and above

BU

0510

14 = Process controller actual value

57 = reserved from SK 540E and above

BU

0510

15 = Process controller setpoint

Further functions are listed in the corresponding supplementary instructions (BU0510 for
POSICON, BU550 for PLC).

Pos: 110 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P547

– Funktion Bus-Sollwert 2 [bis SK 535E] @ 0\mod_1328098180008_388.docx @ 11962 @ @ 1

P547

Func. bus-set point 2

(Function of bus - setpoint 2)

up to SK 535E

S

P

0 ... 55

{ 0 }

This parameter is identical to P546.

Pos: 111 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P548

– Funktion Bus-Sollwert 3 [bis SK 535E] @ 0\mod_1328098278323_388.docx @ 11985 @ @ 1

P548

Func. bus-set point 3

(Function of bus - setpoint 3)

up to SK 535E

S

P

0 ... 55

{ 0 }

This parameter is identical to P546.