9 Telegram examples

BU 0020 GB-2612

93

9.2 Enable with 50% setpoint

A frequency inverter in the "Standby" status must be enabled for clockwise rotation with 50% setpoint.
The last response telegram was received as follows in the controller.

Procedure:

Check last status word (ZSW 0B 31)

Generate control word (STW 04 7F) and specify setpoint (SW1 20 00 (=50%))

Check response telegram (ZSW 0B 37, IW1 20 00)

Details:

Starting requirement (status word of frequency inverter):

Word

5

6

Byte

8

9

10

11

Designation

ZSW

IW1

Value

0B

31

00

00

The following telegram must be sent to the frequency inverter:

Word

5

6

Byte

8

9

10

11

Designation

STW

SW1

Value

04

7F

20

00


The frequency inverter accelerates the motor in the ramp. When the inverter reaches 50% setpoint, it
responds with the following telegram.

Word

5

6

Byte

8

9

10

11

Designation

ZSW

IW1

Value

0B

37

20

00

Note

The status of MFR 1 is indicated in Bit 10 of the response telegram. Depending on the
programmed function and status, the status word may differ.