P546 bus setpoint 1, P547 bus setpoint 2, P548 bus setpoint 3 – NORD Drivesystems BU0020 User Manual

Page 58

Advertising
background image

PROFIBUS DP

– Supplementary manual options for NORD - Frequency Inverters

58

BU 0020 GB-2612

P546

Bus setpoint 1

(Bus setpoint 1)

SK 300E /

SK 7x0E

S

P

0 ... 7

{ 1 }

In this parameter, a function is allocated to the output setpoint 1 during bus actuation. The
settings 2 to 6 are only relevant for type SK 700E and SK 750E inverters in combination with the
POSICON option.

0 = Off

1 = Setpoint frequency (16 bit)

2 = 16 Bit setpoint position

3 = 32 Bit Bit setpoint position (PPO

type 2 or 4)

4 = POSICON control terminals (16 Bit)

6

5 = Setpoint position (16 Bit)

6 = Setpoint position (32 Bit) increment

7 = Bus I/O In Bits 0-7

Pos: 83 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P547

– Bus-Sollwert 2 [SK 300E, SK 7x0E] @ 1\mod_1335788467112_388.docx @ 24976 @ @ 1

P547

Bus setpoint 2

(Bus setpoint 2)

SK 300E /

SK 7x0E

S

P

0 ... 20

{ 0 }

In this parameter, a function is allocated to the setpoint 2 which is output during bus actuation.

0 = Off

11 = Torque precontrol (only SK 7x0E)

(P214)

1 = Setpoint frequency

12 = POSICON control terminals (only

SK 7x0E)

2 = Torque current limit (P112)

13 = Multiplication (only SK 7x0E)

3 = Actual frequency PID

14 = Process controller actual value

4 = Frequency addition

15 = Process controller setpoint

5 = Frequency subtraction

16 = Process controller lead

6 = Current limit (only SK 7x0E) (P536)

17 = BusIO In Bits 0...7

7 = Maximum frequency (only SK 7x0E)

(P105)

18 = Curve

travel

calculator

(only

SK 7x0E)

8 = Actual PID frequency limited

19 = Set relays (P541)

9 = Actual PID frequency monitored

20 =

Set analog output (P542)

10 =

Torque

Pos: 84 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P548

– Bus-Sollwert 3 [SK 300E, SK 7x0E] @ 1\mod_1335790742656_388.docx @ 25000 @ @ 1

P548

Bus setpoint 3

(Bus setpoint 3)

SK 300E /

SK 7x0E

S

P

0 ... 20

{ 0 }

In this parameter, a function is assigned to the delivered setpoint 3 (SW3) for bus control. This is
identical to parameter P547 and is only present if P546 ≠ 3 and 6.

Pos: 85 /Anleitungen/5. Parametrierung/5.8 Informationen @ 0\mod_1328170311705_388.docx @ 12293 @ 3 @ 1

6

The "reference run", "teach-in" and "reset position can be controlled via the other bits:

Bit 0:

Position array / Position increment

Bit 1:

Position array / Position increment

Bit 2:

Position array / Position increment

Bit 3:

Position array / Position increment

Bit 4:

Position array / Position increment

Bit 5:

Position array / Position increment

Bit 6:

Approach reference point

Bit 7:

Reference point

Bit 8:

Teach- In

Bit 9:

Quit Teach- In

Bit 10:

Reset position