Led display with the technology unit – NORD Drivesystems BU0020 User Manual

Page 90

Advertising
background image

PROFIBUS DP

– Supplementary manual options for NORD - Frequency Inverters

90

BU 0020 GB-2612

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Module

– ID

PROFIBUS=06

hex

Module ready

Connection to master

Initialisation active

Reserved (0)

Module error

Timeout error

Reserved (0)

Reserved (0)

LED display with the technology unit:

The status of the PROFIBUS technology unit is indicated by the two built-in LEDs:

Green LED

BR  Bus Ready

Red LED

BE  Bus Error

Meaning

... slow flashing = 1Hz (1s cycle), rapid flashing = 2Hz (0.5s cycle)

ON

OFF

Normal operation; cyclic transfer of data via the PROFIBUS.

ON

ON

Faulty operation; e.g. the PPO type was changed during operation.

Slow flashing

OFF

Process data has not yet been received after switch-on
 e.g. no connection to master

Slow flashing

Brief illumination

Initialisation of the PROFIBUS module (on switch-on or change to
a Profibus parameter on the frequency inverter)

Slow flashing

ON

Timeout in process data reception: the Watchdog time
parameterised in the Profibus master has expired without the
reception of new process data for a maximum of 3s (e.g. baud rate
not detected, cable break).

Slow flashing

Slow flashing

Timeout in process data reception: The time set in P513 has
expired without new process data being received

Slow flashing

Rapid flashing

software version 3.3 R0 and
above

Communication between the
inverter and the PROFIBUS
module has been interrupted.

ON

Slow flashing

up to software version 3.2 R0

Pos: 142 /Anleitungen/Bussysteme/8. Beispiel- Telegramme/!Kapitel Beispiel- Telegramme @ 1\mod_1336400823408_388.docx @ 25786 @ 1 @ 1