6 Parameterisation

BU 0020 GB-2612

65

0 =

Off

13 = ... 16 Reserved

1 =

Actual frequency

17 = Value analog input 1

2 =

Actual speed

18 = Value analog input 2

3 =

Current

19 = Setpoint frequency master

value(P503)

4 =

Torque current (100% = P112)

20 = Setpoint frequency master value after

ramp "Setpoint frequency master
value after ramp"

5 =

Digital IO status

7

21 = Act. freq. without slip master value

"Actual frequency without slip master
value"

6 =

... 7 Reserved

22 = Speed encoder 
 (only possible with

SK 520E and encoder feedback)

8 =

Setpoint frequency

23 = Actual frequency with slip, "Actual

frequency with slip"

(SW V2.0 and above)

9 =

Error number

24 = Master value, actual freq. with slip,

"Master value, actual freq. with slip"

(SW V2.0 and above)

10 = ... 11 Reserved

53 = ... 57 Reserved

12 = BusIO Out Bits 0...7

Further functions are listed in the corresponding supplementary instructions (BU0510 for
POSICON, BU550 for PLC).

Pos: 106 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P544

– Bus-Istwert 2 [bis SK 535E] @ 0\mod_1328097766412_388.docx @ 11870 @ @ 1

P544

Bus actual value 2

(Actual bus value 2)

up to SK 535E

S

P

0 ... 24

{ 0 }

This parameter is identical to P543.

Condition is PPO 2 or PPO 4 type (P507).

Pos: 107 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P545

– Bus-Istwert 3 [bis SK 535E] @ 0\mod_1328097880052_388.docx @ 11893 @ @ 1

P545

Bus actual value 3

(Actual bus value 3)

up to SK 535E

S

P

0 ... 24

{ 0 }

This parameter is identical to P543.

Condition is PPO 2 or PPO 4 type (P507).

Pos: 108 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P546

– Funktion Bus-Sollwert 1 [bis SK 535E] @ 0\mod_1328097962990_388.docx @ 11916 @ @ 1

P546

Func. bus-set point 1

(Function of bus - setpoint 1)

up to SK 535E

S

P

0 ... 55

{ 1 }

In this parameter, a function is allocated to the output setpoint 1 during bus actuation.

The possible analog functions can be found in the following table.

NOTE:

Further details can be found in the respective BUS operating instructions or in the

description of P400.

Pos: 109 /Anleitungen/5. Parametrierung/Parameter/P500-P599/Parameter P546

– Funktion Bus-Sollwerte [ab SK 540E] @ 0\mod_1328098077630_388.docx @ 11939 @ @ 1

7

The assignment of the digital inputs in P543/ 544/ 545 = 5

Bit 0 = DigIn 1

Bit 1 = DigIn 2

Bit 2 = DigIn 3

Bit 3 = DigIn 4

Bit 4 = DigIn 5

Bit 5 = DigIn 6 (SK 520E and above) Bit 6 = DigIn 7 (SK 520E and above)

Bit 7 = Dig. func. AIN1

Bit 8 = Dig. func. AIN1 AIN2

Bit 9 = DigIn 8 (SK 540E and above)

Bit 10 = DigIn 1, 1.IOE (SK 540E and above)

Bit 11 = DigIn 2, 1.IOE (SK 540E and above)

Bit 12 = Out 1/ MFR1

Bit 13 = Out 2/ MFR2

Bit 14 = Out 3/ DOUT1 (SK 520E and above)

Bit 15 = Out 4/ DOUT2 (SK 520E and above)