7 Data transmission

BU 0020 GB-2612

79

Both setpoints are transferred as whole numbers in the range -32768 to 32767. The value 16384
(4000 HEX) corresponds to 100%. The value C000 HEX is equal to

–100%, so that setpoints in the

range

–200% to +200% can be transferred. A setpoint of 100% corresponds to the respective nominal

value:

Setting

100% is equal to

Off

Setpoint frequency, actual frequency PID, actual
frequency PID limited, actual frequency PID monitored,
frequency addition, frequency subtraction, maximum
frequency

Maximum frequency

Torque current limit

Torque current limit (P112)

Current limit

Inverter rated current

Servo mode torque

Rated torque

Torque precontrol

Torque precontrol (P214)

In addition, posicon control bits can also be transferred here (see Setpoint 1)