Grout the baseplate – Goulds Pumps IC - IOM User Manual

Page 29

Advertising
background image

NOTICE: The specified permitted reading values are valid only at operating temperature. For cold
settings, other values are permitted. You must use the correct tolerances. Failure to do so can result in
misalignment and reduced pump reliability.

Perform complete alignment for a vertical correction

A unit is in complete alignment when both the angular indicator (A) and the parallel indicator (P) do not
vary by more than 0.002 in. (0.05 mm) as measured at four points 90° apart.
1. Set the angular and parallel dial indicators to zero at the top-center position (12 o’clock) of the driver

coupling half (Y).

2. Rotate the indicators to the bottom-center position (6 o’clock).
3. Record the indicator readings.
4. Make corrections according to the separate instructions for angular and parallel alignment until you

obtain the permitted reading values.

Perform complete alignment for a horizontal correction

A unit is in complete alignment when both the angular indicator (A) and the parallel indicator (P) do not
vary by more than 0.002 in. (0.05 mm) as measured at four points 90° apart.
1. Set the angular and parallel dial indicators to zero at the left side of the driver coupling half (Y), 90°

from the top-center position (9 o’clock).

2. Rotate the indicators through the top-center position to the right side, 180° from the start position

(3 o’clock).

3. Record the indicator readings.
4. Make corrections according to the separate instructions for angular and parallel alignment until you

obtain the permitted reading values.

Grout the baseplate

Required equipment:

• Cleaners: Do not use an oil-based cleaner because the grout will not bond to it. See the instructions

provided by the grout manufacturer.

• Grout: Non-shrink grout is recommended.

NOTICE: It is assumed that the installer who grouts the baseplate has knowledge of acceptable methods.
More detailed procedures are described in various publications, including API Standard 610, 10th Edition,
Appendix L; API RP 686, Chapter 5; and other industry standards.

1. Clean all the areas of the baseplate that will come into contact with the grout.
2. Build a dam around the foundation.
3. Thoroughly wet the foundation that will come into contact with the grout.
4. Pour grout through the grout hole into the baseplate up to the level of the dam.

When you pour the grout, remove air bubbles from it by using one of these methods:

• Puddle with a vibrator.
• Pump the grout into place.

5. Allow the grout to set.

Installation

Model IC, ICI, ICH, ICIH Installation, Operation, and Maintenance Manual

27

Advertising