Bypass-piping considerations – Goulds Pumps IC - IOM User Manual

Page 37

Advertising
background image

Check

Explanation/comment

Checked

The check valve prevents damage to the pump and

seal due to the back flow through the pump, when

the drive unit is shut off. It is also used to restrain

the liquid flow.
See Example: Discharge piping equipment for

illustrations.

If increasers are used, check that they

are installed between the pump and the

check valve.

See Example: Discharge piping equipment for

illustrations.

If quick-closing valves are installed in

the system, check that cushioning

devices are used.

This protects the pump from surges and water

hammer.

Example: Discharge piping equipment

Correct

Incorrect

1

2

3

4

1.

Bypass line

2.

Shut-off valve

3.

Check valve

4.

Discharge isolation valve

2

1

1.

Check valve (incorrect position)

2.

The isolation valve should not be positioned
between the check valve and the pump.

Bypass-piping considerations

When to use a bypass line

Provide a bypass line for systems that require operation at reduced flows for prolonged periods. Connect a
bypass line from the discharge side (before any valves) to the source of suction.

When to install a minimum-flow orifice

You can size and install a minimum-flow orifice in a bypass line in order to prevent bypassing excessive
flows. Consult your ITT representative for assistance in sizing a minimum-flow orifice.

When a minimum-flow orifice is unavailable

Consider an automatic recirculation control valve or solenoid-operated valve if a constant bypass
(minimum-flow orifice) is not possible.

Installation

Model IC, ICI, ICH, ICIH Installation, Operation, and Maintenance Manual

35

Advertising