4 operatng parameters -4, 5 fuel selecton -4, 4 operating parameters – Bacharach PCA 2 24-9448 User Manual

Page 24: 5 fuel selection

Advertising
background image

Instruction 24-9448

3-4

Initial Setup

3.4 Operating Parameters

The PCA 2 s set up at the factory for the followng operatng parameters:

Fuel . . . . . . . . . . . . . . . . . . . . .Natural Gas

Temperature Unts . . . . . . . . .°F

Pressure Unts . . . . . . . . . . . .Inches of Water Column (nwc)

Polluton Unts . . . . . . . . . . . .ppm

Date . . . . . . . . . . . . . . . . . . . . .Current MM/DD/YY

Tme . . . . . . . . . . . . . . . . . . . .Current EST HH:MM AM/PM

O

2

Reference . . . . . . . . . . . . . .0%

Prnt Pressure . . . . . . . . . . . .No

Zoom . . . . . . . . . . . . . . . . . . . .No

Battery Charger . . . . . . . . . . .OFF

Loggng . . . . . . . . . . . . . . . . . .No

Button Sound . . . . . . . . . . . . .ON

To change any of these parameters, perform the assocated procedure pro-

vded n Sectons 3.5 thru 3.16.

3.5 Fuel Selection

To assure the accurate calculaton of combuston

effcency, select the fuel beng burned as follows:

1. Dsplay the MAIN MENU by pressng the

MENU (F2) button. If necessary, press ESC

untl MENU appears above F2.

2. Use the buttons to hghlght FUEL, and

then press ENT to dsplay the FUEL MENU.

3. Use the buttons to scroll through the

lst of avalable fuels untl the desred

fuel s hghlghted. In the example shown,

PROPANE has been selected.

TIP: Use the buttons to quickly scroll to the

bottom and top of the list.

4. Press ENT to save the selecton and dsplay

the Combuston Test HOLD screen. Observe

that the name of the selected fuel should now

appear at the top of the screen.

MAIN MENU

FUEL

PRESSURE
MEMORY
SETUP
CALIBRATION
DIAGNOSTICS
STATUS

F1

F2

F3

MENU

FUEL MENU

NATURAL GAS
OIL #2
OIL #4
OIL #6

PROPANE

COAL
WOOD

(more)

MENU

F1

F2

F3

Advertising